MODEL: 18KJM
/S: With power switch
Rack-mounted DCS Signal Conditioners 18K-RACK
RELATED PRODUCTS
• Programming Unit (model: PU-2x)
POTENTIOMETER CONVERTER
(field-programmable)
• PC configurator software (model: JXCON)
Downloadable at M-System’s web site.
A dedicated cable is required to connect the module to the
PC. Please refer to the internet software download site or
the users manual for the PC configurator for applicable
cable types.
Functions & Features
• Segment linearization characteristics are freely
configurable via programming unit
• Module can be retracted without removing wiring for an
insulation test
• Optional power switch
GENERAL SPECIFICATIONS
Construction: Rack-mounted; terminal access via screw
terminals on the front and connector on the rear; terminal
cover provided
Connection
Input: M3.5 screw terminals (torque 0.8 N·m)
and connector
Output 1: Connector
Output 2: M3.5 screw terminals (torque 0.8 N·m)
and connector
MODEL: 18KJM–166–R[1]
Power input: Supplied from connector
Screw terminal: Nickel-plated steel
ORDERING INFORMATION
• Code number: 18KJM-166-R[1]
Isolation: Input to output 1 to output 2 to power
Linearization: 16 points max. within the range of -15.00 –
+115.00 % input or output; represented as percentage of
full-scale
Specify a code from below for [1].
(e.g. 18KJM-166-R/S)
• Linearization data (max. 16 points)
Use Ordering Information Sheet (No. ESU-1669) to specify
linearization data when the I/O signals are non-linear.
Adjustments: Programming Unit (model: PU-2x);
linearization data (Unused resistance of the potentiometer's
total resistance can be programmed with the linearization
table.), zero and span, simulating output, etc.
(Refer to the users manual of JXCON for the adjustments
configurable with JXCON.)
INPUT POTENTIOMETER
1: Total resistance 100 Ω – 10 kΩ
OUTPUT 1
Voltage
INPUT SPECIFICATIONS
Minimum span: 25 % of total resistance (set with the
Programming Unit [model: PU-2x] or PC configurator
software [model: JXCON])
6: 1 – 5 V DC (Load resistance 2000 Ω min.)
Excitation: 0.25 V DC
OUTPUT 2
Voltage
6: 1 – 5 V DC (Load resistance 2000 Ω min.)
INSTALLATION
Current consumption: Approx. 60 mA
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Standard Rack 18KBXx
Weight: 150 g (0.33 lb)
POWER INPUT
DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
PERFORMANCE in percentage of span
Accuracy: ±0.1 % with segment gain ≤ 1 [±0.1 % × gain]
with segment gain > 1
[1] OPTIONS
Power Switch
blank: None
18KJM SPECIFICATIONS
ES-0465 Rev.2 Page 1/3
http://www.m-system.co.jp/