S P R I N K L E R
S Y S T E M S
M O N I T O R I N G
Zonecheck
Flow Switch Tester
Manifold Models
Zonecheck Manifold Model
UL/FM Models
ULC Models
with
with
110 V Pump
110 V Pump
ZC20
ZC25
ZC30
ZC40
ZC20A
ZC25A
ZC30A
ZC40A
Retrofit Models
UL/FM Models
ULC Models
International
Models with
220V Pump
with
with
110V Pump
110V Pump
ZCR20
ZCR25
ZCR30
ZCR40
ZCR60
ZCR80
ZCR20A
ZCR25A
ZCR30A
ZCR40A
ZCR60A
ZCR80A
ZCR20E
ZCR25E
ZCR30E
ZCR40E
ZCR60E
ZCR80E
Replacement Parts
ZCK-1 Zonecheck 110V Keyswitch
ZCK-1E Zonecheck 220V Keyswitch
ZCK-1EG Zonecheck 220V Keyswitch (German)
ZCP-110 Zonecheck 110V Pump
ZCP-220 Zonecheck 220V Pump
ZCRK Zonecheck Replacement Kit
Product Overview
Simplifies compliance to NFPA 25 for
quarterly flow switch testing
System Sensor’s Zonecheck flow switch tester is an automatic method for
performing quarterly flow switch tests per NFPA 25.
Does not require opening the inspector’s
test connection
Code Compliance. Quarterly flow switch tests are mandated by NFPA 25.
Zonecheck simplifies testing by re-circulating the water within the pipe around
the flow switch, to simulate the flow of one sprinkler head in operation. This
simulation is achieved without having to open the inspector’s test connection.
Saves as much as 400 gallons of water
per flow switch per year
Environmental Savings. Zonecheck re-circulates the water within the pipe, so no
water is expelled from the system. Over the course of one year, Zonecheck can
save as much as 400 gallons of water per flow switch, per year.
Does not activate the building’s fire pump
Testing initiated by a key switch
Key switches may be interconnected
to control all Zonechecks from one
master switch
Ensured Life Safety. Since Zonecheck does not require opening the inspector’s
test connection, a building’s fire pump is not activated, to avoid unnecessary fire
department dispatches. This also reduces the likelihood of the fire pump being
turned off manually during flow switch testing, thereby ensuring the sprinkler
system’s integrity.
Significantly reduces testing time
Includes a System Sensor flow switch
with each model
Time Savings. Zonecheck’s pump is activated by the turn of a key switch. The
key switch may be wired to initiate one pump locally, or can be interconnected.
When interconnected, any key switch may activate all Zonecheck pumps, to
significantly reduce testing time.
Offered in manifold and retrofit
configurations
Applications Flexibility. All Zonechecks are equipped with a System Sensor flow
switch. Models include manifold and retrofit configurations with either 110V or
220V pumps, and UL, ULC, or International style flow switches.