Time Delay Relays
Dedicated - Single Shot
TSS SERIES
Accessories
Specifications
Time Delay
P1015-18 Quick Connect to Screw Adapter
Range
Repeat Accuracy
Tolerance
(Factory Calibration)
Reset Time
0.05s - 600s in 4 adjustable ranges or fixed
2% or 20ms, whichever is greater
Screw adapter terminal designed for use with
all modules with 0.±5 in. (6.35 mm) male quick
connect terminals.
≤ 5%
≤ 150ms
≤ 20ms
C103PM (AL) DIN Rail
35 mm aluminum DIN rail available in a 36 in.
(91.4 cm) length.
Initiate Time
Time Delay vs Temp.
& Voltage
Input
Voltage
≤ 10%
P1023-20 DIN Rail Adapter
Allows module to be mounted on a 35 mm DIN
type rail with two #10 screws.
24, 120, or 230VAC
20%
Tolerance
AC Line Frequency
Power Consumption
Output
50/60 Hz
≤ 2VA
Selection Guide
Type
Solid state
Form
NO, closed during timing
1A steady state, 10A inrush at 60°C
≅ 5mA @ 230VAC
Maximum Load Current
Off State Leakage Current
Voltage Drop
Protection
≅ 2.5V @ 1A
Circuitry
Encapsulated
Dielectric Breakdown
Insulation Resistance
Mechanical
≥ 2000V RMS terminals to mounting surface
≥ 100 MΩ
Mounting
Dimensions
Surface mount with one #10 (M5 x 0.8) screw
H 50.8 mm (2.0”); W 50.8 mm (2.0”);
D 30.7 mm (1.21”)
Termination
Environmental
Operating/Storage
Temperature
Humidity
0.25 in. (6.35 mm) male quick connect terminals
Function Diagram
- 40° to 75°C / - 40° to 85°C
95% relative, non-condensing
≅ 2.4 oz (68 g)
SINGLE SHOT
(PULSE FORMER)
Weight
V = Voltage
S1 = Initiate Switch
NO = Normally
Open Contact
NC = Normally
Closed Contact
TD =Time Delay
R = Reset
© 2016 Littelfuse Protection Relays & Controls
www.littelfuse.com/tss
Rev: 1-A-062216