Description
TheTSD94110SB retriggerable single-shot timer is designed
for a variety of appllcations. Its digital circuit provides long or
short delays with accuracy and stability over a wide voltage and
temperature range. It is the ideal timer for pulse-train monitoring
of programmable controllers, or any system requiring motion
detection.
Operation AType
Power must be applied to input at all times prior to and
during timing. Upon closure of initiate switch (momentary or
maintained) the load is energized and the time delay is started.
On completion of the delay period the load is de-energized.
Should the initiate switch be reclosed during timing, the delay
will be reset to zero and restarted.
Wiring Diagram
INPUT
Operation BType
LOAD
Upon application of input power, the load is energized and a
time delay is started. At the end of the time delay, the load is
de-energized. Should the initiate switch be closed or reclosed
during timing, the delay is reset to zero and restarted.
3
4
2
5
1
6
Features & Benefits
ꢀJ
Excellent PulseTrain Monitor
ꢀJ
Totally Solid State and Encapsulated
ꢀJ
INITIATE
Microcontroller Circuitry
R
T
ꢀJ
Fast Reset to Zero DuringTiming
NOTE: R is used when external adjustment is ordered.
T
ꢀJ
Excellent Accuracy and Reliability
ꢀJ
DC Units are Reverse Polarity Protected
Specifications
Time Delay
Mechanical
Type
Range
Microcontroller circuitry
Factory fixed 10s
0.5%
Mounting
Termination
Surface mount with one #8 or #1O screw
0.25 in. (6.35 mm) male quick connect
terminals
Molded housing with encapsulated circuitry
H 50.80 mm (2.00”); W 50.80 mm (2.00”);
D 30.70 mm (1.21”)
Repeat Accuracy
Tolerance
(Factory Calibration)
Recycle Time
Time Delay vs. Temp.
& Voltage
Initiate Timing
Input
Operating Voltage
Tolerance
Output
Package
Dimensions
1%
300ms max.
Environmental
Operating/Storage
Temperature
Humidity
2%
16ms max. AC
-40°C to 60°C / -40°C to 85°C
95% relative, non-condensing
Approx. 2.4 oz (68 g)
120 volts AC
15%
Weight
Type
Solid State
Form
Rating
Normally open
1 ampere steady state, 10 amperes inrush
at 55°C
Function Diagram
RETRIGGERABLE SINGLE SHOT
(MOTION DETECTOR) (PSE)
V = Voltage
Voltage Drop
Protection
AC 2.5 volts typical at 1 ampere
S1 = Initiate Switch
NO = Normally
Open Contact
NC = Normally
Closed Contact
t = Incomplete
Time Delay
Transient
Dielectric
Insulation Resistance
Protected
1500 volts RMS
100 megohms minimum 4.4
TD =Time Delay
R = Reset
© 2016 Littelfuse Protection Relays & Controls