SM 3000 Series
3 0 0 0 W AT T S P R O G R A M M A B L E D C S U P P LY
Features
• Constant voltage and constant current operation
• Parallel operation master/slave
• EMC standard EN61204-3
• CE marked
• Optional ethernet, RS232, IEEE 488 programming
• IEEE 488 programming option
• Ethernet, RS232 option
Specifications
OPERATING
INPUT
Efficiency
87%–91%
100kHz
Yes
Input voltage
342-457Vac 3 phase.
48Hz–62Hz
Switching frequency
Thermal protection
Programming
Frequency
Inrush current
Isolation
5.8A @ 400Vac input.
Analogue Programming of voltage and current by
0-5V. IEEE488 programming with external
interface controller PSC44M
I/P to O/P: 3750V rms (8mm creepage),
I/P – Case: 2500V rms, O/P – Case: 600VDC
OUTPUT
Programming speed
See table
Output voltage
See table.
Master/Slave operation
Parallel and series operation with equal current
and voltage sharing. In this way two or more SM-
units can together be used as one high power
unit. Voltage and current of the units is controlled
by the master (by potentiometers or by
Output voltage adjustment 0%–100%
Output current See table.
Output current adjustment 0%–100%
programming). Series operation up to 600V
Resolution
0.03% voltage and current control with 10 turn
Metering
Digital meters standard
potentiometers.
Overvoltage protection
Yes. Trip range user adjustable 0%–115% of V
max.
Indicators
CV/CC mode, OVP triggered LEDs
BATTERY CHARGING
Overload protection
Yes
The CV/CC regulated power supplies are very suitable for battery charging.
Ask for the special datasheet “BATTERY CHARGING WITH SM-series POWER
SUPPLIES”. This datasheet contains information about protective measures
against accidental battery reversing.
Short Circuit protection
Temperature coefficient
Yes
CV: 10x10-6 to 35x10-6 / °C,
CC: 20x10-6 to 60x10-6 / °C.
ENVIRONMENTAL
Load regulation
Line regulation
Ripple & Noise
Stability
0%–100% load see table
Line 10% – see table
Operating temperature
Cooling
-20°C to 50°C
Low noise blower, fan speed adapts to
temperature of internal heatsink. (from left to
right).
See table
CV: 2.10-5 to 4.10-5, CC: 3.10-5 to 10.10-5
Output impedance
(0-100kHz)
SM15-200D: < 25mΩ, SM30-100D: < 20mΩ
SM45-70D: < 60mΩ, SM70-45D: < 60mΩ
SM120-25D: < 150mΩ, SM300-10D: < 800mΩ.
STANDARDS AND APPROVALS
Safety standards
EMC standards
EMI standards
MECHANICAL
Mounting
EN60950 / EN61010
EN61204-3, EN61000-6-2
EN61000-6-3 (EN55022B)
Recovery time
Remote sense
(50%–100% load step): 100µS
2V max. per lead compensation (SM 3004 has no
remote sense)
Bench or 19" rack mounting
468