350ꢀ1200 Watts
SHP Series
xppower.com
•
•
•
•
•
•
•
Rugged Industrial Construction
Variable Fan Speed for Noise Reduction
ꢀ40 °C to +70 °C Operation
AC OK, Remote On/Off and Active Current Share
5 V Standby
Screw Terminals
3 Year Warranty
Specification
Input
General
Input Voltage
• 650 W: 80-264 VAC, derate output power
Efficiency
Isolation
• 85% typical
• 3000 VAC input to output, 1500 VAC input
to ground, 500 VDC output to ground
• PFC 70 kHz, main converter 200 kHz,
standby 130 kHz typical
• 350 W: 6.6 W/in , 650 W: 8.2 W/in ,
1000 W: 8.9 W/in
• AC OK, remote on/off, current share
10% <90 VAC, and 20% <85 VAC
350 & 1000 W: 85-264 VAC, derate output
power 10% <90 VAC
Switching Frequency
Power Density
Input Frequency
Input Current
• 47-63 Hz
• 350 W: 3.8 A typical at 115 VAC,
2.1 A typical at 230 VAC,
650 W: 6.5 A typical at 115 VAC,
3.2 A typical at 230 VAC,
1000 W: 10.9 A typical at 115 VAC,
5.1 A typical at 230 VAC
3
3
3
(1)
Signals
MTBF
• 216-275 KHrs to MIL-HDBK-217F at 25 °C,
(1)
GB
Environmental
Operating Temperature • -20 °C to +70 °C, derate linearly from
Inrush Current
Power Factor
• 650 W: 40 A max at 264 VAC
350 & 1000 W: 60 A max at 264 VAC
• >0.9
+50 °C at 2.5% / °C to 50% at +70 °C,
(1)
(1)
Earth Leakage Current • 0.5 mA max 264 VAC/60 Hz
-40 °C start up
Input Protection
• 350W: T10 A/250 V, 650W: T16 A/250 V,
Cooling
• 650 W: Forced cooled, ‘-TF’ & ‘-EF’ models
have integral dual voltage level fan, which is
load dependant, U Channel requires 5.5 m/s
minimum airflow, 350 & 1000 W: Forced cooled
via integral multi voltage level fan which is load
1000W: T20 A/250 V internal fuse in line and
neutral, 350W: single internal fuse in line.
Output
Output Voltage
Output Voltage Trim
Initial Set Accuracy
(1)
• 12-48 VDC (see tables)
dependant
•
10% V1
Operating Humidity
Storage Temperature • -40 °C to +85 °C
Operating Altitude
Shock
Vibration
• 95% RH, non-condensing
• 650 W: 1% V1, 5% V3,
350 & 1000 W: 1% V1, 5% V2
• No minimum load required
• 500 ms max
• 50 ms typical
• 3000 m
Minimum Load
Start Up Delay
Start Up Rise Time
Hold Up Time
Drift
• 30 g pk, half sine, 6 axes EN60068-2-27, -2-47
• 2 g rms, 5-500 kHz, 3 axes EN60068-2-6
• 20 ms minimum
EMC & Safety
Emissions
•
•
0.2% after 20 min warm up
0.5%
• EN55022 class B conducted
EN55022 class A radiated
• EN61000-3-2 class A,
650 W: class C for loads ≥20%
350 & 1000 W: class C for loads ≥10%
• EN61000-3-3
• EN61000-4-2, level 3 contact, level 3 air,
Perf Criteria A
• EN61000-4-3, level 3 Perf Criteria A
• EN61000-4-4, level 3 Perf Criteria A
• EN61000-4-5, installation class 3,
Perf Criteria A
• EN61000-4-6, level 3, Perf Criteria A
• EN61000-4-11, 30% 10 ms,
60% 100 ms, 100% 5000 ms,
Perf Criteria A, B, B
• IEC60950-1 CB report, CSA 22.2
No. 60950-1, UL60950-1, TUV,
EN60950-1, SEMI F47
Line Regulation
Load Regulation
• 650 W: 1% V1, 5% V3,
350 & 1000 W: 1% V1, 5% V2
• 4% max. deviation, recovery to
within 1% in 500 µs for a 50-75-50%
load change
Harmonic Currents
Transient Response
Voltage Flicker
ESD Immunity
Ripple & Noise
• 1% pk-pk typical V1, 20 MHz bandwidth
Overvoltage Protection • 115-145% Vnom, recycle input to reset
Overload Protection
Overtemperature
Protection
Short Circuit Protection • Constant current characteristic
Temp. Coefficient
Remote Sense
Remote On/Off
Radiated Immunity
EFT/Burst
Surge
• 110-140%, V1 only
• Auto reset
(1)
Conducted Immunity
Dips & Interruptions
• 0.05% / °C
• Compensates for 0.5 V total voltage drop
• Uncommitted isolated optocoupler diode,
powered diode inhibits V1 and fan supply
(1)
Safety Approvals
(1)
Current Share
• Single wire current share
(1)
See longform datasheet for more information