240W Single Output Industrial DIN RAIL with PFC Function
SDR-240 series
Features :
High efficiency 94% and low power dissipation
150% peak load capability
Built-in active PFC function, PF>0.93
Protections: Short circuit / Overload / Over voltage / Over temperature
Cooling by free air convection
Built-in constant current limiting circuit
Can be installed on DIN rail TS-35/7.5 or 15
UL 508 (industrial control equipment) approved
EN61000-6-2(EN50082-2) industrial immunity level
Built-in DC OK relay contact
100% full load burn-in test
3 years warranty
PQ
GL
Marine
SPECIFICATION
MODEL
SDR-240-24
SDR-240-48
DC VOLTAGE
24V
48V
RATED CURRENT
CURRENT RANGE
RATED POWER
10A
5A
0 ~ 10A
240W
0 ~ 5A
240W
7.5A
PEAK CURRENT
PEAK POWER Note.6
15A
360W (3sec.)
OUTPUT
RIPPLE & NOISE (max.) Note.2 100mVp-p
VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE Note.3 1.0%
120mVp-p
48 ~ 55V
1.0%
24 ~ 28V
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
0.5%
0.5%
1.0%
1.0%
1500ms, 60ms/230VAC
3000ms, 60ms/115VAC at full load
HOLD UP TIME (Typ.)
VOLTAGE RANGE
20ms/230VAC
88 ~ 264VAC
47 ~ 63Hz
20ms/115VAC at full load
124 ~ 370VDC
FREQUENCY RANGE
POWER FACTOR (Typ.)
EFFICIENCY (Typ.)
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
0.93/230VAC
0.99/115VAC at full load
Note.8 94%
INPUT
2.6A/115VAC
33A/115VAC
<1mA / 240VAC
1.3A/230VAC
65A/230VAC
Normally works within 110 ~ 150% rated output power for more than 3 sec and then shut down o/p voltage with auto-recovery
>150% rated power, constant current limiting with auto-recovery within 2 seconds and may cause to shut down if over 2 seconds
OVERLOAD
56 ~ 65V
29 ~ 33V
OVER VOLTAGE
OVER TEMPERATURE
PROTECTION
Protection type : Shut down o/p voltage with auto-recovery
95
5
(TSW : detect on heatsink of power switch)
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
60Vdc/0.3A, 30Vdc/1A, 30Vac/0.5A resistive load
-25 ~ +70 (Refer to output load derating curve)
20 ~ 95% RH non-condensing
FUNCTION DC OK REALY CONTACT RATINGS (max.)
WORKING TEMP.
Note.5
WORKING HUMIDITY
-20 ~ +85 , 10 ~ 95% RH
ENVIRONMENT STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
0.03%/ (0 ~ 50
Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
VIBRATION
SAFETY STANDARDS
WITHSTAND VOLTAGE
UL508, TUV EN60950-1 approved
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC O/P-DC OK:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25 / 70% RH
ISOLATION RESISTANCE
SAFETY &
EMI CONDUCTION & RADIATION Compliance to EN55022 (CISPR22) Class B
EMC
(Note 4)
HARMONIC CURRENT
Compliance to EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11, ENV50204, EN55024, EN61000-6-2 (EN50082-2), EN61204-3, heavy industry level,
criteria A, SEMI F47, GL approved
EMS IMMUNITY
MTBF
169.3Khrs min. MIL-HDBK-217F (25
63*125.2*113.5mm (W*H*D)
)
OTHERS
NOTE
DIMENSION
PACKING
1.03Kg; 12pcs/13.4Kg/1.06CUFT
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power.
In case the adjacent device is a heat source, 15mm clearance is recommended.
6. 3 seconds max., please refer to peak loading curves.
7. Derating may be needed under low input voltage. Please check the derating curve for more details.
8. After 30 min. of burn-in.
File Name:SDR-240-SPEC 2008-12-17