2400W Parallel (N+1) With PFC Function
SCP-2K4 series
■ Features :
ꢀAC input 180~260VAC, 3ψ3 wire
ꢀAC 220V, 1ψor 380V, 3ψ4 wire(option)
ꢀPF> 0.98@ 230VAC
ꢀProtections: Short circuit / Overload / Over voltage / Over temperature
ꢀBuilt-in remote sense function, remote ON-OFF control
ꢀBuilt-in power good signal output
ꢀBuilt-in parallel operation function(N+1)
ꢀCan adjust from 20~100% output voltage by external control 1-5V
ꢀForced air cooling by built-in DC fan
ꢀCase coating with paint
ꢀ3 years warranty
..
SPECIFICATION
ORDER NO.
SCP-2K4-09 SCP-2K4-12 SCP-2K4-15 SCP-2K4-18 SCP-2K4-24 SCP-2K4-36 SCP-2K4-48 SCP-2K4-60
SAFETY MODEL NO.
2K4S-P009
9V
2K4S-P012
12V
2K4S-P015
15V
2K4S-P018
18V
2K4S-P024
24V
2K4S-P036
36V
2K4S-P048
48V
2K4S-P060
60V
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
266A
200A
160A
133.3A
100A
66.6A
50A
40A
0 ~ 266A
2394W
0 ~ 200A
2400W
0 ~ 160A
2400W
0 ~ 133.3A
2399W
0 ~ 100A
2400W
0 ~ 66.6A
2397W
0 ~ 50A
2400W
200mVp-p
0 ~ 40A
2400W
200mVp-p
OUTPUT
RIPPLE & NOISE (max.) Note.2 90mVp-p
VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE Note.3 2.0%
120mVp-p
150mVp-p
150mVp-p
150mVp-p
200mVp-p
3.0% Typical adjustment by potentiometer
20% ~ 100% adjustment by 1 ~ 5VDC external control
1.0%
0.5%
0.5%
1.0%
0.5%
0.5%
1.0%
0.5%
0.5%
1.0%
0.5%
0.5%
1.0%
0.5%
0.5%
1.0%
0.5%
0.5%
1.0%
0.5%
0.5%
LINE REGULATION
LOAD REGULATION
0.5%
1.5%
SETUP, RISE, HOLD UP TIME 800ms, 400ms, 12ms at full load
VOLTAGE RANGE
FREQUENCY RANGE
POWER FACTOR
180 ~ 260VAC
47 ~ 63Hz
3ψ3 wire (other system available)
>0.98 / 230VAC
83%
INPUT
EFFICIENCY (Typ.)
AC CURRENT
84%
85%
86%
88%
88%
89%
89%
15A / 230VAC
60A / 230VAC
3.5mA / 240VAC
INRUSH CURRENT (max.)
LEAKAGE CURRENT(max.)
110 ~ 140% rated output power
OVERLOAD
Note. 4
Protection type : Current limiting, delay shut down o/p voltage, re-power on to recover
110 ~ 135% Follow to output set up point
PROTECTION OVER VOLTAGE
Protection type : Shut down o/p voltage, re-power on to recover
>100℃ / measure by heat sink, near transformer
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
-20 ~ +65℃ (Refer to output load derating curve)
20 ~ 90% RH non-condensing
OVER TEMPERATURE
WORKING TEMP.
WORKING HUMIDITY
-20 ~ +85℃, 10 ~ 95% RH
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
ENVIRONMENT
0.04% / ℃ (0 ~ 50℃)
10 ~ 200Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
UL60950, TUV EN60950-1 Approved
SAFETY STANDARDS
WITHSTAND VOLTAGE
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, OP/FG:100M Ohms / 500VDC / 25℃/ 70% RH
Compliance to EN55022 (CISPR22) class A
SAFETY & ISOLATION RESISTANCE
EMC
(Note. 5)
EMI CONDUCTION & RADIATION
Compliance to EN61000-3-2,3
HARMONIC CURRENT
EMS IMMUNITY
POWER GOOD SIGNAL
SPECIAL FUNCTION
COOLING
Compliance to EN61000-4-2,3,4,5,6,8,11, Light industry level, criteria A
Open collector of NPN transistor
DC Voltage Adj., Remote sensing, remote control, parallel operation(refer to control terminal instruction manual)
By fan, >20% load or >50℃ fan on
OTHERS
NOTE
MTBF
24.9K hrs min. MIL-HDBK-217F(25℃)
350*212*124mm (L*W*H)
DIMENSION
9.0kg ; 1pcs / 10kg / CARTON
PACKING
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. Current limiting 3 times(1.5s,3.0s,5.0s)Then intelligent auto recovery before shut down
5. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
File Name:SCP-2K4-SPEC 2007-03-01