Current and Voltage Controls
3 Phase-phase Max. and Min. Voltage Control
Types S 172, SYY 165
• Monitoring relay and 3-phased measur-
ing relay for upper/lower phase-phase
voltages control
• Measures if all 3 phase-phase voltages are within
set limits
• Measures on own power supply
• Operates irrespective of phase sequence
• Upper and lower limits separately adjustable
• Built-in adjustable timer function
• Output: 10 A SPDT relay
• Plug-in type module
• S-housing
• LED-indication for power supply and output ON
• Power supply is the 3-phased measuring voltage
Product Description
3-phase monitoring plug-in (or incorrect) in order to se- Housing
relay for separate upper and cure the equipment. The Type
lower voltage control. Often S 172 features built-in time Output
used where the generated delay.
electrical power is unstable
Ordering Key
S 172 156 220
Power supply
Type Selection
Plug
Output
Timer
Supply: 220 VAC
S 172 156 220
SYY 165 220
Supply: 380 VAC
S 172 156 380
SYY 165 380
Supply: 400 VAC
S 172 156 400
Supply: 415 VAC
S 172 156 415
SYY 165 415
Circular SPDT
Circular SPDT
Yes
No
Input Specifications
Output Specifications
Input
Pins 5, 6 & 7
Output
Rated insulation voltage
SPDT relay
250 VAC (rms)
Arbitrary phase sequence
(cont./elect.)
Measuring ranges (VAC)
Power supply (phase-phase) 3 x 220 3 x 380 3 x 400
Contact ratings (AgCdO)
µ (micro gap)
± 15%
± 15%
± 15%
Resistive loads
AC 1
10 A/250 VAC (2500 VA)
1 A/250 VDC (250 W)
10 A/25 VDC (250 W)
2.5 A/230 VAC
5 A/24 VDC
≥ 30 x 106 operations
Range
Upper level
Scale
Lower level
Scale
Power supply (phase-phase) 3 x 415
187-253 323-437 340-460
231-253 399-437 420-460
105-115%105-115%105-115%
187-209 323-361 340-480
85-95% 85-95% 85-95%
DC 1
or
Small inductive loads AC 15
DC 13
Mechanical life
Electrical life
AC 1
≥ 2.5 x 105 operations
(at max. load)
± 15%
353-477
Range
Upper level
Scale
Lower level
Scale
436-477
105-115%
353-394
85-95%
measures average value of
own supply, whereas scale
ranges are calibrated to
rms-value
Operating frequency
Dielectric strength
Dielectric voltage
Rated impulse withstand volt. 4 kV (1.2/50 µs) (cont./elect.)
(IEC 60664)
≤ 7200 operations/h
≥ 2 kVAC (rms) (cont./elect.)
Voltage interruption
Dielectric voltage
≤ 40 ms
None (supply/elect.)
Rated impulse withstand volt. 4 kV (1.2/50 µs) (line/neutral,
line/line), direct connection
to electronics
Specifications are subject to change without notice (26.10.99)
1