MODEL: R5-TS1A
I/O: Euro type connector terminal
Remote I/O R5 Series
(Applicable wire size: 0.2 – 2.5 mm
2
(AWG24 - 12),
stripped length 7 mm)
THERMOCOUPLE INPUT MODULE
Internal power: Via the base (model: R5-BS)
Isolation: Input to output to internal bus or internal power
Zero/Span adj. mode selector: Rotary switch; monitor mode,
adj. mode and simulated output mode selectable
Sensor type: Selectable with the side DIP SW
Temperature unit: °C, °F or absolute temperature selectable
with the side DIP SW
(re-transmitted output)
18 (.71)
2
3
4
1
5
0
7 6
9
8
90
(3.54)
Burnout detection: Upscale or downscale selectable with the
side DIP SW
96.5
(3.80)
Linearization: Standard
mm (inch)
Cold junction compensation: CJC sensor attached to the
input terminals
RUN indicator: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
MODEL: R5-TS1A[1][2]
ORDERING INFORMATION
• Code number: R5-TS1A[1][2]
Specify a code from below for each of [1] and [2].
(e.g. R5-TS1AW/Q)
INPUT SPECIFICATIONS
Input resistance: 30 kΩ min.
• Specify the specification for option code /Q
(e.g. /C01)
Burnout sensing: ≤ 0.1 μA
Temperature range
°C
T/C
USABLE
RANGE
CONFORMANCE
RANGE
NO. OF CHANNELS
1: 1 channel
K (CA) (*)*1
E (CRC) *1
-272 to +1472
-272 to +1120
-260 to +1300
-272 to +500
24 to 1920
-150 to +1370
-170 to +1000
-180 to +1200
-170 to +400
400 to 1760
200 to 1760
0 to 1760
J
(IC)
(CC) *1
T
B (RH) *1
OUTPUT
Current
R
-100 to +1860
-100 to +1860
-52 to +2416
-272 to +1400
-252 to +700
-252 to +1000
-52 to +1496
-52 to +1860
S
A: 4 – 20 mA DC (Load resistance 600 Ω max.)
C (WRe 5-26)
N *1
0 to 2315
-130 to +1300
-200 to +600
-200 to +900
0 to 1395
U
[1] COMMUNICATION MODE
S: Single
L
P (Platinel II)
(PR)
0 to 1760
W: Dual
°F
T/C
USABLE
RANGE
CONFORMANCE
RANGE
K (CA) *1
E (CRC) *1
-458 to +2682
-458 to +2048
-436 to +2372
-458 to +932
75 to 3488
-238 to +2498
-274 to +1832
-292 to +2192
-274 to +752
752 to 3200
392 to 3200
32 to 3200
[2] OPTIONS
blank: none
J
(IC)
(CC) *1
/Q: With options (specify the specification)
T
B (RH) *1
R
-148 to +3380
-148 to +3380
-62 to +4381
-458 to +2552
-422 to +1292
-422 to +1832
-62 to +2725
-62 to +3380
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
S
C (WRe 5-26)
N *1
32 to 4199
-202 to +2372
-328 to +1112
-328 to +1652
32 to 2543
U
/C02: Polyurethane coating
L
P (Platinel II)
(PR)
/C03: Rubber coating
32 to 3200
(*) Factory setting. Set the input range within 0-1000°C
corresponding to the output range 0-10000.
*1. Accuracy degrades at temperatures close to the lower
limit of the usable range.
GENERAL SPECIFICATIONS
Connection
Internal bus: Via the Installation Base (model: R5-BS)
Max. (upscale) or min. (downscale) value of the usable
range when a burnout is detected.
R5-TS1A SPECIFICATIONS
ES-7571 Rev.8 Page 1/4
http://www.m-system.co.jp/