MODEL: R3-NM1
Remote I/O R3 Series
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
MODBUS INTERFACE MODULE
/C02: Polyurethane coating
27.5 [1.08]
/C03: Rubber coating
EX-FACTORY SETTING
/SET: Preset according to the Ordering Information Sheet
(No. ESU-8354)
130
[5.12]
PACKAGE INCLUDES...
• Terminating resistor (110 Ω, 0.25 W)
109
[4.29]
mm [inch]
GENERAL SPECIFICATIONS
Connection
Modbus: Euro type connector terminal
MODEL: R3-NM1-[1][2]
(applicable wire size: 0.2 to 2.5 mm , stripped length 7 mm)
2
Internal bus: Via the Installation Base
(model: R3-BSx)
ORDERING INFORMATION
• Code number: R3-NM1-[1][2]
Specify a code from below for each of [1] and [2].
(e.g. R3-NM1-R/CE/Q)
Internal power: Via the Installation Base (model: R3-BSx)
Power input, RUN contact output: M3 separable screw
terminal (torque 0.5 N·m)
• Specify the specification for option code /Q
(e.g. /C01/SET)
Screw terminal: Nickel-plated steel
Isolation: Modbus to internal bus or internal power to power
input to RUN contact output to FG
Input error data: Input value setting at input module error
with side DIP SW
[1] POWER INPUT
N: No power supply
Main/Sub switching control in dual communication mode:
Selectable with the side DIP SW (refer to the manual)
Dual communication setting: Set with the side DIP switch
Data allocation setting: Set with the side DIP switch
RUN indicator: Bi-color (green/red) LED; Green ON in normal
communication; Red ON when receiving data (Function
selected with DIP SW)
AC Power
K3: 100 – 120 V AC
(Operational voltage range 85 - 132 V, 47 - 66 Hz) *
(CE not available)
L3: 200 – 240 V AC
(Operational voltage range 170 - 264 V, 47 - 66 Hz) *
(CE not available)
ERR indicator: Bi-color (green/red) LED; Green blinking / ON
(0.1 sec.) at communication or setting error; Red ON at
transmitting data (Function selected with DIP SW)
■ RUN CONTACT OUTPUT
DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.) *
* Not selectable for use with independent power modules or
network modules with the internal power input options.
• ON when RUN indicator is green (Modbus in normal
communication)
Rated load: 250 V AC @ 0.5 A (cos ø = 1)
30 V DC @ 0.5 A (resistive load)
[2] OPTIONS (multiple selections)
Standards & Approvals
blank: Without CE
(Less than 50 V AC to conform with EU Directive)
Maximum switching voltage: 250 V AC or 30 V DC
Maximum switching power: 250 VA or 150 W
Minimum load: 1 V DC @ 1 mA
/CE: CE marking
Other Options
blank: none
Mechanical life: 2 × 10 cycles (300 cycles/min.)
7
/Q: Option other than the above (specify the specification)
When driving an inductive load, external contact protection
and noise quenching recommended.
R3-NM1 SPECIFICATIONS
ES-8354 Rev.24 Page 1/8
https://www.m-system.co.jp/