360W Single Output Battery Charger
PB-360 series
Features :
3 stage charging
AC 115/230VAC selected by switch
Built-in passive PFC function compliance to EN61000-3-2 Class A (option)
Protection: Short circuit / Reverse polarity / Over voltage / Over temperature
Charger for lead-acid batteries
2 color LED loading indicator
Low cost, High reliability
FAN on/off control(Depends on charging current)
3 years warranty
(except for 48V)
(P type only)
PB 360 P
12
12:14.4V
24:28.8V
48:57.6V
P:With Passive PFC
N:Without Passive PFC
SPECIFICATION
MODEL
PB-360 -12
PB-360 -24
PB-360 -48
BOOST CHARGE VOLTAGE 14.4V
28.8V
57.6V
FLOAT CHARGE VOLTAGE 13.6V
27.2V
54.4V
VOLTAGE ADJUSTABLE RANGE 13 ~ 14.7V
26 ~ 28.8V
52 ~ 58.6V
OUTPUT
RECOMMENDED BATTERY
80 ~ 240Ah
CAPACITY(AMP HOURS) Note 5
40 ~ 125Ah
20 ~ 65Ah
BATTERY TYPE
Open & Sealed Lead Acid
OUTPUT CURRENT (Typ.) Note 6 24.3A
12.5A
6.25A
VOLTAGE RANGE
90 ~ 132VAC / 180 ~ 264VAC selected by switch
127 ~ 187VDC / 254 ~ 370VDC
FREQUENCY RANGE
EFFICIENCY (Typ.)
47 ~ 63Hz
85%
86%
87%
INPUT
POWER FACTOR (Typ.)
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
>0.65 (with P type) at 230VAC
7A/115VAC
3.5A/230VAC
COLD START 60A
<3.5mA / 240VAC
LEAKAGE CURRENT
SHORT CIRCUIT
O/P Built in fuse (FS100) to protect short circuit condition, shut down o/p voltage and can not re-power on
By internal fuse
REVERSE POLARITY
16 ~ 18V
31 ~ 35V
59 ~ 64V
PROTECTION
OVER VOLTAGE
Protection type : Shut down o/p voltage, re-power on to recover
Protection type : Automatically derate charge current until zero
OVER TEMPERATURE
REMOTE CONTROL (CN5)
WORKING TEMP.
FUNCTION
Open: Normal work
Short: Stop Charging
-20 ~ +60 (Refer to output load derating curve)
20 ~ 90% RH non-condensing
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
-40 ~ +85 , 10 ~ 95% RH
ENVIRONMENT
0.05%/ (0 ~ 45
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
IEC60335-2-29 CB approved by TUV(except for 48V), UL60950-1 approved
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
SAFETY STANDARDS
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
SAFETY &
EMC
(Note 4)
EMI CONDUCTION & RADIATION Compliance to EN55022 (CISPR22) Class B
HARMONIC CURRENT
EMS IMMUNITY
MTBF
Compliance to EN61000-3-2,-3 (only P type)
Compliance to EN61000-4-2,3,4,5,6,8,11; ENV50204, EN55024, light industry level, criteria A
115.8Khrs min. MIL-HDBK-217F (25
253*135*48.5mm(L*W*H)
)
OTHERS
NOTE
DIMENSION
PACKING
1.5Kg; 6pcs/10Kg/0.95CUFT
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. This is Mean Well's suggested range. Please consult your battery manufacturer for their suggestions about maximum charging current limitation.
6. Maximum charging current will be in the range of 90~110% rated output current.
File Name:PB-360-SPEC 2010-04-12