360W Single Output Battery Charger
PB-360 series
Features :
3 stage charging
AC 115/230VAC selected by switch
Built-in passive PFC function compliance to EN61000-3-2 Class A (option)
Protection: Overload / Short circuit / Reverse polarity / Over voltage
/ Over temperature
Charger for lead-acid batteries
2 color LED loading indicator
Low cost, High reliability
FAN on/off control(Depends on charging current)
2 years warranty
(except for 48V)
(P type only)
PB 300/360 P
12
1.300W without FAN
2.360W with FAN
12:14.4V
24:28.8V
48:57.6V
P:With Passive PFC
N:Without Passive PFC
SPECIFICATION
MODEL
PB-360 -12
PB-360 -24
PB-360 -48
BOOST CHARGE VOLTAGE 14.4V
28.8V
57.6V
FLOAT CHARGE VOLTAGE 13.6V
27.2V
54.4V
VOLTAGE ADJUSTABLE RANGE 13 ~ 14.7V
26 ~ 28.8V
52 ~ 58.6V
OUTPUT
RECOMMENDED BATTERY
80 ~ 200Ah
CAPACITY(AMP HOURS)(Note 5)
40 ~ 125Ah
20 ~ 65Ah
BATTERY TYPE
Open & Sealed Lead Acid
OUTPUT CURRENT
24.3A
12.5A
6.25A
VOLTAGE RANGE
90 ~ 132VAC / 180 ~ 264VAC selected by switch
47 ~ 63Hz
248 ~ 370VDC
FREQUENCY RANGE
EFFICIENCY (Typ.)
85%
86%
87%
INPUT
POWER FACTOR (Typ.)
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
>0.65 (with P type) at 230VAC
7A/115VAC
3.5A/230VAC
COLD START 60A
LEAKAGE CURRENT
<3.5mA / 240VAC
90 ~ 110% rated output current
OVERLOAD
Protection type : Constant current limiting, recovers automatically after fault condition is removed
O/P Built in fuse (FS100) to protect short circuit condition, shut down o/p voltage and can not re-power on
By internal fuse
SHORT CIRCUIT
PROTECTION REVERSE POLARITY
16 ~ 18V
31 ~ 35V
59 ~ 64V
OVER VOLTAGE
Protection type : Shut down o/p voltage, re-power on to recover
Protection type : Automatically derate charge current until zero
OVER TEMPERATURE
FUNCTION
Open: Normal work
Short: Stop Charging
REMOTE CONTROL (CN5)
-20 ~ +60 (Refer to output load derating curve)
20 ~ 90% RH non-condensing
WORKING TEMP.
WORKING HUMIDITY
ENVIRONMENT
-40 ~ +85 , 10 ~ 95% RH
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
0.05%/ (0 ~ 45
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
IEC60335-2-29 CB approved by TUV(except for 48V), UL60950-1 approved
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
SAFETY STANDARDS
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
SAFETY &
EMC
(Note 4)
EMI CONDUCTION & RADIATION Compliance to EN55022 (CISPR22) Class B
HARMONIC CURRENT
EMS IMMUNITY
MTBF
Compliance to EN61000-3-2,-3 (only P type)
Compliance to EN61000-4-2,3,4,5,6,8,11; ENV50204, EN55024, light industry level, criteria A
115.8Khrs min. MIL-HDBK-217F (25
253*135*48.5mm(L*W*H)
)
OTHERS
NOTE
DIMENSION
PACKING
1.5Kg; 6pcs/10Kg/0.95CUFT
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. This is Mean Well's suggested range. Please consult your battery manufacturer for their suggestions about maximum charging current limitation.
File Name:PB-360-SPEC 2008-11-11