Heavy current
MULTIBOX UPB 160A
https://www.schurter.com /PG13_14_15
Multibox UPB 160A, DIN 00
See below:
Approvals and Compliances
Description
Characteristics
- With 3 x 1-pole fuse switch disconnector
- Bolt lock (4-kant with Slot)
- Glass fiber Polyester
- Difficult to burn
- Impact resistant
- Protection 2-piece, transparent and sealable
- N-connector for TN-C to TN-S
- N-connector separating Piece self-opening when loosening the screw
- Voltage test possible only if fuse with not insulated straps used
Unique Selling Proposition
- Direct mounting on formwork for uncomplicated concreting , tested
with flow cement SVB
- Wall thickness adjustable from 18 to 25 centimeters
- filled with styrofoam - all around tight, so that no concrete water can
penetrate
References
Alternative: Other rated current
Weblinks
pdf data sheet, html datasheet, Detailed request for product, Microsite
Customer Specific Solutions
Whether surface or flush-mounted, with Multibox you always work with the same housings and fuse elements (60A) or switch-disconnectors (DIN00).
The additional housings, which can be attached with one click, give you maximum flexibility with a minimum of effort.
Smart Meetering MULTIBOX is up to the
increased requirements. The energy
meters of the latest generation of lea-
ding manufacturers fit perfectly into the role of the Building Entry Point (BEP).
housingthe MULTIBOX. This is how the The flexible concept of MULTIBOX takes
power distributors see the power supply both a combined power cable with Speed wing screws.
and the energy measurement centrally
at the point of entry into the building at
a glance.
Fiber to the Home MULTIBOX introduces MULTIBOX UPB The MULTIBOX UPB can
MULTIBOX UPB After the pipes have been
new technologies optimally and space-
saving into the building.It takes on the
be set in concrete directly with the simp- installed, the MULTIBOX can be set in
lest means. The UPB version is mounted concrete. As soon as the formwork is
on the formwork in a few easy steps and stripped, the polystyrene block is remo-
adjusted to the wall thickness with the
ved and the safety elements are installed
and connected. The front frame and the
cover form the end.
Pipes as well as a separate fiber optic
cable to the building.
Technical Data
Rated Current Ie
160A @ 500VAC
125A@ 690VAC
Rated Impulse Withstand Vol- 8kV
tage Uimp
Conditioned Rated Short Cicuit 50kA @ 500VAC
Current
Rated voltage Ue
690VAC
1000VAC
50Hz
Rated isolation voltage Ui
Rated Power Operating Fre-
quency fe
Rated short-time withstand
current with fuse links
20kA @ 500VAC
Allowed Ambient Temperature -25°C to +40°C acc. to IEC 61439
Protection by closed housing IP54
Terminals
NH-Fuse-Link with Screw Ter- M8
minal for Cable Log
Neutral Disconnector with
Straps
6 - 70mm²
Fuse Element with double ter- 6 - 70mm²
minals strap
Earth Connection Bride
Double erminal
Earth Connection (outside)
6 - 70mm²
6 - 50mm²
M8
1