40W Single Output Industrial DIN Rail Power Supply
MDR-40 series
Features :
Universal AC input/Full range
Protections: Short circuit / Overload / Over voltage
Cooling by free air convection
Can be installed on DIN rail TS-35/7.5 or 15
NEC class 2 / LPS compliant (12V,24V,48V only)
LED indicator for power on
DC OK relay contact
No load power consumption<0.75W
100% full load burn-in test
3 years warranty
SPECIFICATION
MODEL
MDR-40-5
MDR-40-12
MDR-40-24
MDR-40-48
DC VOLTAGE
5V
12V
24V
48V
RATED CURRENT
CURRENT RANGE
RATED POWER
6A
3.33A
1.7A
0.83A
0 ~ 6A
30W
0 ~ 3.33A
0 ~ 1.7A
40.8W
150mVp-p
24 ~ 30V
1.0%
0 ~ 0.83A
39.8W
200mVp-p
48 ~ 56V
1.0%
40W
RIPPLE & NOISE (max.) Note.2 80mVp-p
VOLTAGE ADJ. RANGE 5 ~ 6V
VOLTAGE TOLERANCE Note.3 2.0%
120mVp-p
OUTPUT
12 ~ 15V
1.0%
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
1.0%
1.0%
1.0%
1.0%
1.0%
1.0%
1.0%
1.0%
Note.5 500ms, 30ms/230VAC
500ms, 30ms/115VAC at full load
HOLD UP TIME (Typ.)
VOLTAGE RANGE
50ms/230VAC
85 ~ 264VAC
47 ~ 63Hz
78%
20ms/115VAC at full load
120 ~ 370VDC
FREQUENCY RANGE
EFFICIENCY (Typ.)
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
86%
88%
88%
INPUT
1.1A/115VAC
0.7A/230VAC
COLD START 30A/115VAC
<1mA / 240VAC
60A/230VAC
105 ~ 150% rated output power
OVERLOAD
Protection type : Constant current limiting, recovers automatically after fault condition is removed
6.25 ~ 7.25V 15.6 ~ 18V 31.2 ~ 36V
PROTECTION
57.6 ~ 64.8V
OVER VOLTAGE
Protection type : Shut down o/p voltage, re-power on to recover
Relay contact rating(max.): 30V/1A resistive
-20 ~ +70 (Refer to "Derating Curve")
20 ~ 90% RH non-condensing
FUNCTION
DC OK SIGNAL
WORKING TEMP.
WORKING HUMIDITY
ENVIRONMENT STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
-40 ~ +85 , 10 ~ 95% RH
0.03%/ (0 ~ 50
Component : 10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes ; Mounting : Compliance to IEC60068-2-6
UL508, UL60950-1, TUV EN60950-1 approved, NEC class 2 / LPS compliant (12V,24V,48V only)
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
VIBRATION
SAFETY STANDARDS
WITHSTAND VOLTAGE
SAFETY &
I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25 / 70% RH
ISOLATION RESISTANCE
EMC EMISSION
EMC IMMUNITY
MTBF
EMC
(Note 4)
Compliance to EN55011, EN55022 (CISPR22), EN61204-3 Class B, EN61000-3-2,-3
Compliance to EN61000-4-2, 3, 4, 5, 6, 8, 11, EN55024, EN61000-6-2, EN61204-3, heavy industry level, criteria A
301.7K hrs min. MIL-HDBK-217F (25
40*90*100mm (W*H*D)
)
OTHERS
NOTE
DIMENSION
0.3Kg; 42pcs/13.6Kg/0.82CUFT
PACKING
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. Length of set up time is measured at first cold start. Turning ON/OFF the power supply may lead to increase of the set up time.
File Name:MDR-40-SPEC 2011-05-24