MODEL: M60SVS
Base-free Interconnecting Ultra-Slim Signal Conditioners M60S Series
OUTPUT – Field-selectable
Current
4 – 20 mA DC (Load resistance 550 Ω max.)
0 – 20 mA DC (Load resistance 550 Ω max.)
Voltage
SIGNAL TRANSMITTER
(field-configurable)
Functions & Features
0 – 10 V DC (Load resistance 10 kΩ min.)
2 – 10 V DC (Load resistance 10 kΩ min.)
0 – 5 V DC (Load resistance 5000 Ω min.)
1 – 5 V DC (Load resistance 5000 Ω min.)
• Converts DC input from a sensor into a standard process
signal
• Output range and response time selectable with DIP SW
• Power connector for interconnecting modules and
collectively supplying power
• Spring clamp terminal connection for easy wiring
• 6-mm wide ultra-slim design
POWER INPUT
DC Power
• Low profile allows mounting in a 120-mm deep panel
• High-density mounting
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
• Power indicator LED
8 (.31)
[1] OPTIONS
blank: none
/Q: Options other than the above (specify the specification)
108 (4.25)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
102 (4.02)
/C02: Polyurethane coating
GENERAL SPECIFICATIONS
Connection
MODEL: M60SVS-R[1]
Input and output: Spring clamp terminal
Power input: Via the power connector or the spring clamp
terminal
ORDERING INFORMATION
• Code number: M60SVS-R[1]
Specify a code from below for [1].
(e.g. M60SVS-R/Q)
Applicable wire size: 0.2 to 1.5 mm , stripped length 8 mm
2
Housing material: Flame-resistant resin (black)
Isolation: Input to output to power
Zero adjustment: -2 to +2 % (front)
• Specify the specification for option code /Q
(e.g. /C01)
Span adjustment: 98 to 102 % (front)
Power LED: Green LED turns on when the power is supplied.
• Default at shipment
Input range: 4 – 20 mA DC
Output range: 4 – 20 mA DC
Response time: Standard response
INPUT SPECIFICATIONS
■ DC Current: Input resistor incorporated
INPUT – Field-selectable
Current
INSTALLATION
Power consumption: Max. 0.6 W
4 – 20 mA DC (Input resistance 50 Ω)
0 – 20 mA DC (Input resistance 50 Ω)
Voltage
Power input: Max. 3 A (Total current consumed by the
interconnected signal conditionerse must be 3 A or less.)
Operating temperature: -20 to +55°C (-4 to +131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: DIN rail
0 – 10 V DC (Input resistance 200 kΩ min.)
2 – 10 V DC (Input resistance 200 kΩ min.)
0 – 5 V DC (Input resistance 100 kΩ min.)
1 – 5 V DC (Input resistance 100 kΩ min.)
Weight: 65 g (2.3 oz)
M60SVS SPECIFICATIONS
ES-8022 Rev.1 Page 1/3
http://www.m-system.co.jp/