5秒后页面跳转
M2XR2-4Z1-R PDF预览

M2XR2-4Z1-R

更新时间: 2024-11-07 02:23:43
品牌 Logo 应用领域
爱模 - MSYSTEM /
页数 文件大小 规格书
4页 115K
描述
Super-mini Signal Conditioners Mini-M Series

M2XR2-4Z1-R 数据手册

 浏览型号M2XR2-4Z1-R的Datasheet PDF文件第2页浏览型号M2XR2-4Z1-R的Datasheet PDF文件第3页浏览型号M2XR2-4Z1-R的Datasheet PDF文件第4页 
MODEL: M2XR2  
Note: Consult M-System for 2-wire RTD  
Super-mini Signal Conditioners Mini-M Series  
(Configurator software is used to change input type and  
temperature range.)  
RTD TRANSMITTER  
(PC programmable)  
[2] OUTPUT  
Functions & Features  
Current  
• Accepts direct input from an RTD and provides a standard  
process signal  
Z1: Range 0 – 20 mA DC  
Voltage  
• PC programmable  
V1: Range -2.5 – +2.5 V DC  
• User’s temperature table can be used  
• Leadwire resistance compensation  
V2: Range -10 – +10 V DC  
(Configurator software is used to change output over the  
described range of the selected suffix code. For changing  
out of this range, set the Output Range Selectors inside the  
unit before software adjustment.)  
Typical Applications  
• Long distance transmission between the RTD and the  
transmitter  
• Combination with intrinsic safety barriers  
[3] POWER INPUT  
AC Power  
23 (.91)  
M2: 100 – 240 V AC (Operational voltage range 85 – 264 V,  
47 – 66 Hz)  
(90 – 264 V for UL)  
M
od  
el  
76  
(2.99)  
DC Power  
R: 24 V DC  
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)  
P: 110 V DC  
124  
(4.88)  
(Operational voltage range 85 – 150 V, ripple 10 %p-p max.)  
(110 V ±10 % for UL)  
mm (inch)  
[4] OPTIONS (multiple selections)  
Burnout  
MODEL: M2XR2–[1][2]–[3][4]  
blank: Upscale burnout  
ORDERING INFORMATION  
• Code number: M2XR2-[1][2]-[3][4]  
Specify a code from below for each [1] through [4].  
(e.g. M2XR2-4Z1-R/BL/CE/Q)  
/BL: Downscale burnout  
(UL not available)  
/BN: No burnout  
(UL not available)  
Input Code 4: Pt 100 (JIS ’97, IEC) setting will be used if the  
input code is not specified.  
Standards & Approvals (must be specified)  
/N: Without CE or UL  
• Temperature range (e.g. 0 – 500°C)  
• Output range (e.g. 4 – 20 mA DC)  
• Specify the specification for option code /Q  
(e.g. /C01/S01)  
/CE: CE marking  
/UL: UL approval, CE marking  
Other Options  
blank: none  
/Q: Option other than the above (specify the specification)  
[1] INPUT RTD (2- or 3-wire)  
1: JPt 100 (JIS'89)  
SPECIFICATIONS OF OPTION: Q (multiple selections)  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
3: Pt 100 (JIS'89)  
4: Pt 100 (JIS'97, IEC)  
5: Pt 50 Ω (JIS'81)  
/C02: Polyurethane coating  
6: Ni 508.4 Ω  
/C03: Rubber coating (UL not available)  
TERMINAL SCREW MATERIAL  
7: Pt 1000  
8: Ni 100  
/S01: Stainless steel (UL not available)  
9: Cu 10 @25°C  
0: Specify (Please provide a resistance table.)  
M2XR2 SPECIFICATIONS  
ES-5087 Rev.11 Page 1/4  
http://www.m-system.co.jp/  

与M2XR2-4Z1-R相关器件

型号 品牌 获取价格 描述 数据表
M2XR2-4Z1-R/BL MSYSTEM

获取价格

Super-mini Signal Conditioners Mini-M Series
M2XR2-4Z1-R/BN MSYSTEM

获取价格

Super-mini Signal Conditioners Mini-M Series
M2XR2-4Z1-R/CE MSYSTEM

获取价格

Super-mini Signal Conditioners Mini-M Series
M2XR2-4Z1-R/N MSYSTEM

获取价格

Super-mini Signal Conditioners Mini-M Series
M2XR2-4Z1-R/Q MSYSTEM

获取价格

Super-mini Signal Conditioners Mini-M Series
M2XR2-4Z1-R/UL MSYSTEM

获取价格

Super-mini Signal Conditioners Mini-M Series
M2XR2-5V1-M2 MSYSTEM

获取价格

Super-mini Signal Conditioners Mini-M Series
M2XR2-5V1-M2/BL MSYSTEM

获取价格

Super-mini Signal Conditioners Mini-M Series
M2XR2-5V1-M2/BN MSYSTEM

获取价格

Super-mini Signal Conditioners Mini-M Series
M2XR2-5V1-M2/CE MSYSTEM

获取价格

Super-mini Signal Conditioners Mini-M Series