MODEL: M2PP
Super-mini Signal Conditioners Mini-M Series
[3] OUTPUT LOGIC
N: The same as the input
R: Inverted
PULSE ISOLATOR
Functions & Features
• Galvanically isolates pulse rate signals
• Input frequency = output frequency
• Various outputs (open collector, voltage pulses and dry
contact AC/DC switch)
[4] POWER INPUT
AC Power
M: 85 – 264 V AC (Operational voltage range 85 – 264 V,
47 – 66 Hz)
(Select ‘/N’ for ‘Standards & Approvals’ code.)
M2: 100 – 240 V AC (Operational voltage range 85 – 264 V,
47 – 66 Hz)
Typical Applications
• Isolating field pulse signals in order to reduce noises
• Changing e.g. dry contact signal to e.g. 5 V signals
(‘/UL’ is not selectable for ‘Standards & Approvals’ code.)
DC Power
23 (.91)
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
R2: 11 – 27 V DC
Model
76
(2.99)
(Operational voltage range 11 – 27 V, ripple 10 %p-p max.)
(Select ‘/N’ for ‘Standards & Approvals’ code.)
P: 110 V DC
(Operational voltage range 85 – 150 V, ripple 10 %p-p max.)
(‘/UL’ is not selectable for ‘Standards & Approvals’ code.)
124
(4.88)
mm (inch)
[5] OPTIONS (multiple selections)
Standards & Approvals (must be specified)
/N: Without CE or UL
MODEL: M2PP–[1][2][3]–[4][5]
/CE: CE marking
ORDERING INFORMATION
• Code number: M2PP-[1][2][3]-[4][5]
Specify a code from below for each of [1] through [5].
(e.g. M2PP-33N-M2/CE/Q)
/UL: UL approval, CE marking
Other Options
blank: none
/Q: Option other than the above (specify the specification)
• Specify the specification for option code /Q
(e.g. /C01/S01)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
[1] INPUT
1: Mechanical contact (max. 30 Hz)
2: Open collector (max. 10 kHz)
3: Voltage pulse (max. 10 kHz)
9: Clamp-on pulse sensor CLSP
(‘/UL’ is not selectable for ‘Standards & Approvals’ code.)
/C02: Polyurethane coating
/C03: Rubber coating (UL not available)
TERMINAL SCREW MATERIAL
/S01: Stainless steel (UL not available)
RELATED PRODUCTS
• Clamp-on pulse sensor (model: CLSP)
[2] OUTPUT
1: Low frequency open collector (max. 30 Hz)
2: High frequency open collector (max. 10 kHz)
3: 5 V pulse (max. 10 kHz)
4: 12 V pulse (max. 10 kHz)
5: 24 V pulse (max. 10 kHz)
7: Dry contact AC/DC switch (max. frequency 30 Hz)
(‘/UL’ is not selectable for ‘Standards & Approvals’ code.)
M2PP SPECIFICATIONS
ES-5061 Rev.22 Page 1/4
http://www.m-system.co.jp/