MODEL: LTWTN  
= 6.666 × 10–3 [kWh/pulse]  
= 6.666 [Wh/pulse]  
Power Transducer Series LT-UNIT  
Check that the required pulse unit is within the available  
frequency range, 0.006 – 3.12 Hz.  
Input Range [W] ÷ (Calculated Pulse × 3600[s])  
= 750 ÷ (6.666 × 3600)  
WATT TRANSDUCER  
(self-powered)  
Functions & Features  
• Provides a DC output signal and a pulse totalizer signal in  
proportion to AC active power  
= 0.03125 [Hz]  
• Convenient pulse unit output (Wh×10  
n)  
[1] CONFIGURATION  
1: 3-phase / 3-wire  
• Measuring bidirectional power flow  
• DC output containing little ripple is ideal for computer  
input  
2: Single-phase / 2-wire  
3: Single-phase / 3-wire  
4: 3-phase / 4-wire  
• “Time division multiplication” method accepts distorted  
waveforms  
• Isolation up to 2000 V AC  
• High-density mounting  
[2] VT INPUT (unbalanced load)  
For 3-phase / 4-wire, phase voltages (e.g. 110 V / √3 ) are used.  
1: 110 V AC  
• Conforms to IEC 60688  
• No auxiliary power supply required  
(Not selectable for single-phase/3-wire system.)  
2: 220 V AC  
Typical Applications  
• Centralized monitoring and control of power management  
system in a manufacturing facility or building  
• SCR – Silicon Controlled Rectifier  
(Not selectable for single-phase/3-wire system.)  
4: 220 V / 380 V AC (3-phase/4-wire only)  
A: 100 V / 200 V AC  
(single-phase / 3-wire only)  
72  
(2.83)  
[3] CT INPUT (unbalanced load)  
Current  
1: 1 A AC  
2: 2 A AC  
5: 5 A AC  
111  
(4.37)  
[4] DC OUTPUT  
143 (5.63)  
Current  
mm (inch)  
A: 4 – 20 mA DC (Load resistance 500 Ω max.)  
D: 0 – 20 mA DC(Load resistance 500 Ω max.)  
F: 0 – 10 mA DC (Load resistance 1000 Ω max.)  
G: 0 – 1 mA DC (Load resistance 10 kΩ max.)  
J: 0 – 5 mA DC (Load resistance 2000 Ω max.)  
FW: -10 – +10 mA DC (Load resistance 1000 Ω max.)  
GW: -1 – +1 mA DC (Load resistance 10 kΩ max.)  
JW: -5 – +5 mA DC (Load resistance 2000 Ω max.)  
Z: Specify current (See OUTPUT SPECIFICATIONS)  
Voltage  
MODEL: LTWTN–[1][2][3][4][5][6]  
ORDERING INFORMATION  
• Code number: LTWTN–[1][2][3][4][5][6]  
Specify a code from below for each of [1] through [6].  
(e.g. LTWTN-115A2/T/Q)  
• Special output range (For codes Z & 0)  
• Specify the specification for option code /Q  
(e.g. /C01)  
1: 0 – 10 mV DC (Load resistance 10 kΩ min.)  
2: 0 – 100 mV DC (Load resistance 100 kΩ min.)  
3: 0 – 1 V DC (Load resistance 1000 Ω min.)  
4: 0 – 10 V DC (Load resistance 10 kΩ min.)  
5: 0 – 5 V DC (Load resistance 5000 Ω min.)  
6: 1 – 5 V DC (Load resistance 5000 Ω min.)  
1W: -10 – +10 mV DC (Load resistance 10 kΩ min.)  
2W: -100 – +100 mV DC (Load resistance 100 kΩ min.)  
• Use Ordering Information Sheet (No. ESU-3355).  
How to determine Pulse Unit  
[Example]  
3-phase / 3-wire, VT 3300/110 V, CT 250/5 A, calibration  
range 750 W  
10 [kWh/pulse] ÷ ((3300÷110) × (250÷5))  
LTWTN SPECIFICATIONS  
ES-3356 Rev.13 Page 1/5  
https://www.m-system.co.jp/  

与LTWTN-11530/Q相关器件

型号 品牌 获取价格 描述 数据表
LTWTN-11530/T MSYSTEM

获取价格

Power Transducer Series LT-UNIT
LTWTN-11531 MSYSTEM

获取价格

Power Transducer Series LT-UNIT
LTWTN-11531/Q MSYSTEM

获取价格

Power Transducer Series LT-UNIT
LTWTN-11531/T MSYSTEM

获取价格

Power Transducer Series LT-UNIT
LTWTN-11532 MSYSTEM

获取价格

Power Transducer Series LT-UNIT
LTWTN-11532/Q MSYSTEM

获取价格

Power Transducer Series LT-UNIT
LTWTN-11532/T MSYSTEM

获取价格

Power Transducer Series LT-UNIT
LTWTN-11540 MSYSTEM

获取价格

Power Transducer Series LT-UNIT
LTWTN-11540/Q MSYSTEM

获取价格

Power Transducer Series LT-UNIT
LTWTN-11540/T MSYSTEM

获取价格

Power Transducer Series LT-UNIT