5秒后页面跳转
LPNE-55/Q PDF预览

LPNE-55/Q

更新时间: 2024-11-28 02:46:31
品牌 Logo 应用领域
爱模 - MSYSTEM /
页数 文件大小 规格书
2页 104K
描述
Power Transducer Series L-UNIT

LPNE-55/Q 数据手册

 浏览型号LPNE-55/Q的Datasheet PDF文件第2页 
MODEL: LPNE  
Power Transducer Series L-UNIT  
[3] OPTIONS  
blank: none  
/Q: With options (specify the specification)  
PT TRANSDUCER  
(self-powered, RMS sensing)  
Functions & Features  
SPECIFICATIONS OF OPTION: Q (multiple selections)  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
• Converting an alternating voltage from a potential  
(voltage) transformer into a standard process signal  
• Minimum ripple  
/C02: Polyurethane coating  
• No auxiliary power source required  
• Isolation up to 2000 V AC  
/C03: Rubber coating  
TERMINAL SCREW MATERIAL  
/S01: Stainless steel  
• High-density mounting  
Typical Applications  
GENERAL SPECIFICATIONS  
Construction: Stand-alone; terminal access at the front  
Connection: M3.5 screw terminals (torque 0.8 N·m)  
Screw terminal: Nickel-plated steel (standard) or stainless  
steel  
• Centralized monitoring and control of power line and  
power supply voltages measured at switch boards  
• Monitoring abnormal voltage drops for detecting overload  
Housing material: Flame-resistant resin (black)  
Isolation: Input to output  
75  
(2.95)  
Input waveform: Up to 15 % of 3rd harmonic content  
Overrange output: 60 – 120 % at 0 – 5 V  
Span adjustment: 95 to 105 % (front)  
75  
(2.95)  
INPUT SPECIFICATIONS  
Frequency: 50 or 60 Hz  
112  
(4.41)  
mm (inch)  
Input burden: 2 VA  
Overload capacity: 150 % of rating for 10 sec., 120 %  
continuous  
Operational range: 60 – 120 % of rating  
MODEL: LPNE–[1][2][3]  
OUTPUT SPECIFICATIONS  
OPERATION DIAGRAM  
ORDERING INFORMATION  
• Code number: LPNE–[1][2][3]  
Specify a code from below for each [1] through [3].  
(e.g. LPNE-55/Q)  
OUT %  
100  
• Specify the specification for option code /Q  
(e.g. /C01/S01)  
50  
0
0
50 (60)  
100  
IN %  
[1] INPUT  
Voltage  
Note: The described accuracy is not assured within 0 – 60%  
of the rating, though output signal exists.  
5: 0 – 150 V AC (used within 90 – 150 V)  
6: 0 – 300 V AC (used within 180 – 300 V)  
INSTALLATION  
[2] OUTPUT  
Current  
Operating temperature: -10 to +55°C (14 to 131°F)  
Operating humidity: 30 to 85 %RH (non-condensing)  
Mounting: Surface or DIN rail  
G: 0 – 1 mA DC (Load resistance 5000 Ω max.)  
Voltage  
Weight: 200 g (0.44 lb)  
3: 0 – 1 V DC (Load resistance 2000 Ω min.)  
4: 0 – 10 V DC (Load resistance 20 kΩ min.)  
5: 0 – 5 V DC (Load resistance 10 kΩ min.)  
http://www.m-system.co.jp/  
LPNE SPECIFICATIONS  
ES-1949 Rev.2 Page 1/2  

与LPNE-55/Q相关器件

型号 品牌 获取价格 描述 数据表
LPNE-5G MSYSTEM

获取价格

Power Transducer Series L-UNIT
LPNE-5G/Q MSYSTEM

获取价格

Power Transducer Series L-UNIT
LPNE-63 MSYSTEM

获取价格

Power Transducer Series L-UNIT
LPNE-63/Q MSYSTEM

获取价格

Power Transducer Series L-UNIT
LPNE-64 MSYSTEM

获取价格

Power Transducer Series L-UNIT
LPNE-64/Q MSYSTEM

获取价格

Power Transducer Series L-UNIT
LPNE-65 MSYSTEM

获取价格

Power Transducer Series L-UNIT
LPNE-65/Q MSYSTEM

获取价格

Power Transducer Series L-UNIT
LPNE-6G MSYSTEM

获取价格

Power Transducer Series L-UNIT
LPNE-6G/Q MSYSTEM

获取价格

Power Transducer Series L-UNIT