Low-Peak™ Class J
LPJ — 600Vac/300Vdc, 70-600A, Dual Element, Time-Delay Fuses
Dimensions - in
4.63"
3.63"
7.13"
5.25"
3.38"
1.13"
0.13"
0.75"
2.63"
0.41"
1.63"
1.88"
*2"
0.25"
1"
0.28"
0.38"
0.53"
225 to 400A
65 to 100A
8.0"
6.0"
3.75"
5.75"
4.38"
3.0"
Available with easyID™
open fuse indication
0.53"
2"
1.13"
0.28"
2.5"
0.38"
1.5"
1.38"
0.19"
2.13"
0.38"
0.69"
450 to 600A
100 to 200A
Description: Ultimate protection Class J dual element,
current-limiting, time-delay fuses available with optional open
fuse indication. Time-delay – 10 seconds (minimum) at 500%
of rated current.
Features:
• Industry’s only UL Listed and CSA Certified fuse with a
300kA Vac interrupting rating that exceeds requirements for
virtually all applications
• Fast short-circuit protection provides optimal arc flash
protection to reduce hazard to personnel
Catalog Symbols:LPJ-(amp)SP (non-indicating)
LPJ-(amp)SPI (indicating)
• Easy selective coordination with all Low-Peak fuses using
simple 2:1 ampacity ratio
Ratings:
• Long time-delay minimizes needless fuse openings due to
temporary overloads and transient surges
• Can often be sized for back-up protection against motor
burnout from overload or single-phasing if other overload
protective devices fail
• High degree of current-limitation due to the fast speed-of-
response to short-circuits
• Faster response to damaging short-circuit currents than
mechanical overcurrent protective devices
Volts — 600Vac, 300Vdc
Amps — 70-600A
IR — 300kA Vac RMS Sym.
— 100kA Vdc
Agency Information:
CE, UL Listed, Guide JDDZ, File E4273
CSA Certified, Class 1422-02, File 53787, Class J per CSA
C22.2 No. 248.8,
• Reduces let-through thermal and magnetic forces in order
to protect low withstand rated components
• Proper sizing provides “no damage” Type “2” coordinated
protection for NEMA and IEC motor control in accordance
with IEC Standard 947-4-1
• Dual-element fuses have lower resistance than ordinary
fuses, hence they run cooler
• Lower watts loss reduces power consumption
• Space-saving package for equipment down sizing
Catalog Numbers (amps) — Non-indicating Fuses*
LPJ-70SP
LPJ-80SP
LPJ-90SP
LPJ-100SP
LPJ-110SP
LPJ-125SP
LPJ-150SP
LPJ-175SP
LPJ-200SP
LPJ-225SP
LPJ-250SP
LPJ-300SP
LPJ-350SP
LPJ-400SP
LPJ-450SP
LPJ-500SP
LPJ-600SP
*
Open fuse indication available on all part numbers by inserting the suffix “I,”
e.g., LPJ-90SPI. Requires 75Vac minimum voltage.
Recommended Fuse Blocks
Fuse Amps
70-100
110-200
225-400
450-600
1-Pole
2-Pole
3-Pole
Carton Quantity and Weight
JM60100-1CR
JM60200-1CR
JM60400-1CR
JM60600-1CR
JM60100-2CR
JM60200-2CR
JM60400-2CR
JM60600-2CR
JM60100-3CR
JM60200-3CR
JM60400-3CR
JM60100-3CR
Amp Rating
70–100
Carton Qty.
5
5
1
1
110–200
225–400
450–600
For additional information on the JM Series of fuse blocks, see
product brochure # 3192.
Fuse Reducers For Class R Fuses
Equipment
Fuse Clips
60A
Desired Fuse
(Case) Size
30A
Catalog Numbers
(Pairs)
J-63
30A
60A
60A
J-13
J-16
J-26†
100A
200A
†
Not for bolt-in applications.
0713
BU-SB13689
Page 1 of 3
Data Sheet # 1007