Low-Peak™ Class J
LPJ — 600Vac/300Vdc, 1-60A, Dual Element, Time-Delay Fuses
Dimensions - in
2.25"
2.38"
( 0.03ꢀ
( 0.03ꢀ
1.06"
0.81"
0.63"
( 0.03ꢀ
0.5"
( 0.03ꢀ
Available with easyID™
open fuse indication
1 to 30A
35 to 60A
Features:
• Industry’s only UL Listed and CSA Certified fuse with a
300kA Vac interrupting rating that exceeds requirements for
virtually all applications
• Long time-delay minimizes needless fuse openings due to
temporary overloads and transient surges
Description: Ultra protection Class J dual element, current-
limiting, time-delay fuses available with optional open fuse in-
dication. Time-delay – 10 seconds (minimum) at 500% of
rated current.
• Easy selective coordination with all Low-Peak fuses using
simple 2:1 ampacity ratio
• Can often be sized for back-up protection against motor
burnout from overload or single-phasing if other overload
protective devices fail
• High degree of current limitation due to the fast speed-of-
response to short-circuits
Catalog Symbol: LPJ-(amp)SP (non-indicating)
LPJ-(amp)SPI (indicating)
Ratings:
Volts — 600Vac, 300Vdc
Amps — 1-60A
• Faster response to damaging short-circuit currents than
mechanical overcurrent protective devices
IR — 300kA Vac RMS Sym.
— 100kA Vdc
• Reduces let-through thermal and magnetic forces in order
to protect low withstand rated components
• Proper sizing provides “no damage” Type “2” coordinated
protection for NEMA and IEC motor control in accordance
with IEC Standard 947-4-1
Agency Information:
CE, UL Listed, Guide JDDZ, File E4273
• Dual-element fuses have lower resistance than ordinary
fuses so they run cooler
• Lower watts loss reduces power consumption
• Space-saving package for equipment downsizing
CSA Certified, Class 1422-02, File 53787,
Class J per CSA 22.2 No. 248.
Catalog Numners (amps) – Non-indicating Fuses
LPJ-1SP
LPJ-11⁄
SP
LPJ-16⁄10SP
LPJ-18⁄10SP
LPJ-2SP
LPJ-3SP
LPJ-7SP*
LPJ-8SP*
LPJ-9SP*
LPJ-10SP*
LPJ-12SP*
LPJ-15SP*
LPJ-25SP*
LPJ-30SP*
LPJ-35SP*
LPJ-40SP*
LPJ-45SP*
LPJ-50SP*
LPJ-60SP*
Recommended Fuse Blocks and Holders
4
LPJ-32⁄10SP
Fuse Amps
1-Pole
2-Pole
3-Pole
LPJ-31⁄
2
SP
LPJ-4SP
LPJ-41⁄
SP
Open Blocks
0-30
35-60
J60030-1
J60060-1
J60030-2
J60060-2
J60030-3
J60060-3
2
LPJ-21⁄
LPJ-21⁄
4
SP
SP
LPJ-5SP
LPJ-56⁄10SP
LPJ-6SP*
“Pyramid” Blocks
2
LPJ-171⁄
2
SP*
0-30
35-60
JP60030-1
JP60060-1
JP60030-2
JP60060-2
JP60030-3
JP60060-3
LPJ-28⁄10SP
LPJ-20SP*
*
Open fuse indication available by inserting the suffix “I,” e.g., LPJ-15SPI.
Requires 75Vac minimum voltage.
CH Series Holders
0-30
35-60
CH30J1
CH60J1
CH30J2
CH60J2
CH30J3
CH60J3
Carton Quantity and Weight
Amp Rating
1–30
Carton Qty.
Safety J™ Holders
JT60030
JT60060
10
10
0-30
35-60
—
—
—
—
35–60
For additional information on the Class J fuse blocks and
holders, see data sheets # 1114 (open blocks), #1108
(pyramid blocks), # 2144 (CH Series) and # 1152 (Safety J).
Fuse Reducers For Class R Fuses
Equipment
Fuse Clips
60A
Desired Fuse
(Case) Size
30A
Catalog Numbers
(Pairs)
J-63
30A
60A
60A
J-13
J-16
J-26†
100A
200A
†
Not for bolt-in applications.
0713
BU-SB13688
Page 1 of 3
Data Sheet # 1006