40W Single Output Switching Power Supply
LPF-40D series
Features :
Universal AC input / Full range (up to 305VAC)
Built-in active PFC function
High efficiency up to 89%
Protections: Short circuit / Over current / Over voltage / Over temperature
Cooling by free air convection
Fully isolated plastic case
Fully encapsulated with IP67 level (Note.6)
Class
power unit, no FG
Class 2 power unit
Built-in 3 in 1 dimming function (1~10Vdc or PWM signal or resistance)
Suitable for LED lighting and moving sign applications
Compliance to worldwide safety regulations for lighting
Suitable for dry / damp / wet locations
3 years warranty
110
F
M
M
SELV
( for 48V,54V only)
( except for 48V,54V )
IP67
SPECIFICATION
MODEL
LPF-40D-12 LPF-40D-15 LPF-40D-20 LPF-40D-24 LPF-40D-30 LPF-40D-36 LPF-40D-42 LPF-40D-48 LPF-40D-54
36V
42V
DC VOLTAGE
12V
15V
20V
24V
30V
48V
54V
21.6 ~ 36V
1.12A
25.2 ~ 42V
0.96A
CONSTANT CURRENT REGION Note.4 7.2 ~12V
9 ~ 15V
2.67A
40.08W
150mVp-p
4.0%
12 ~ 20V
2A
14.4 ~ 24V 18 ~ 30V
28.8 ~ 48V 32.4 ~ 54V
RATED CURRENT
RATED POWER
3.34A
1.67A
1.34A
40.2W
200mVp-p
4.0%
0.84A
0.76A
40.32W
250mVp-p
4.0%
40.32W
250mVp-p
4.0%
40.08W
40W
40.08W
150mVp-p
4.0%
40.32W
250mVp-p
4.0%
41.04W
350mVp-p
4.0%
RIPPLE & NOISE (max.) Note.2 150mVp-p
VOLTAGE TOLERANCE Note.3 4.0%
150mVp-p
4.0%
OUTPUT
0.5%
0.5%
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
0.5%
2.0%
0.5%
0.5%
0.5%
0.5%
0.5%
0.5%
0.5%
0.5%
1.5%
1.0%
0.5%
0.5%
0.5%
0.5%
Note.7 1000ms, 80ms / 115VAC at full load 1000ms, 80ms / 230VAC
HOLD UP TIME (Typ.)
VOLTAGE RANGE
16ms/230VAC
Note.5 90 ~ 305VAC
47 ~ 63Hz
16ms/115VAC at full load
127 ~ 431VDC
FREQUENCY RANGE
POWER FACTOR (Typ.)
EFFICIENCY (Typ.)
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
PF>0.97/115VAC, PF>0.95/230VAC, PF>0.92/277VAC at full load (Please refer to "Power Factor Characteristic" curve)
INPUT
84%
86%
88%
88.5%
89%
89%
85%
88%
87%
0.6A / 115VAC
0.3A / 230VAC
COLD START 75A/230VAC
<0.75mA / 240VAC
95 ~ 108%
OVER CURRENT
Note.4
Protection type : Constant current limiting, recovers automatically after fault condition is removed
Hiccup mode, recovers automatically after fault condition is removed.
SHORT CIRCUIT
OVER VOLTAGE
34 ~ 40V
41 ~ 49V
46 ~ 54V
54 ~ 63V
59 ~ 66V
15 ~ 17V
Protection type : Shut down and latch off o/p voltage, re-power on to recover
90 10 (RTH2)
17.5 ~ 21V 23 ~ 27V
28 ~ 35V
PROTECTION
OVER TEMPERATURE
Protection type : Shut down o/p voltage, re-power on to recover
-40 ~ +70 (Refer to "Derating Curve")
20 ~ 95% RH non-condensing
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
-40 ~ +80 , 10 ~ 95% RH
ENVIRONMENT
0.03%/ (0 ~ 50
)
10 ~ 500Hz, 5G 12min./1cycle, period for 72min. each along X, Y, Z axes
UL8750, CSA C22.2 No. 250.0-08(except for 48V, 54V), EN61347-1, EN61347-2-13 independent, IP67, J61347-1, J61347-2-13
approved ; design refer to UL60950-1, TUV EN60950-1
SAFETY STANDARDS Note.6
SAFETY &
EMC
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMC EMISSION
I/P-O/P:3.75KVAC
I/P-O/P:100M Ohms / 500VDC / 25 / 70% RH
Compliance to EN55015, EN61000-3-2 Class C ( 60% load) ; EN61000-3-3
Compliance to EN61000-4-2,3,4,5,6,8,11; EN61547, EN55024, light industry level(surge 2KV), criteria A
EMC IMMUNITY
MTBF
394.9Khrs min. MIL-HDBK-217F (25
162.5*43*32mm (L*W*H)
)
OTHERS
NOTE
DIMENSION
PACKING
0.45Kg; 32pcs/15.4Kg/0.93CUFT
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. Constant current operation region is within 60% ~100% rated output voltage. This is the suitable operation region for LED related applications, but please
reconfirm special electrical requirements for some specific system design.
5. Derating may be needed under low input voltages. Please check the static characteristics for more details.
6. Suitable for indoor use or outdoor use without direct sunlight exposure. Please avoid immerse in the water over 30 minutes.
7. Length of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time.
8. The power supply is considered as a component that will be operated in combination with final equipment. Since EMC performance will be affected by the
complete installation, the final equipment manufacturers must re-qualify EMC Directive on the complete installation again.
File Name:LPF-40D-SPEC 2012-03-20