xppower.com
150ꢀ500 Watts
LCL Series
•
•
•
•
•
•
•
Single Output Industrial Supplies
High Efficiency
Low Cost
150 W Convection Cooled
300 W & 500 W with Internal Fans
Outputs from 12 V to 48 V
3 Year Warranty
Specification
Input
General
Input Voltage
Input Frequency
Input Current
• 85-264 VAC (127-370 VDC) (see note 1)
• 47-63 Hz
• 2.1 A max for LCL150, 4.5 A max for
LCL300, 6.6 A max for LCL500
• 40 A max for LCL150,
60 A max for LCL300 & 500
cold start at 25 şC, 230 VAC
• >0.9
Efficiency
Isolation
• 88% typical at full load & 230 VAC
• 3000 VAC Input to Output
1500 VAC Input to Ground
500 VAC Output to Ground
Switching Frequency
• 90-110 kHz main converter & 45-190 kHz
PFC for LCL150, 80-190 kHz main converter
& 62-65 kHz PFC for LCL300 & 500
Inrush Current
3
3
Power Density
MTBF
• 2.7 W/in LCL150, 4.4 W/in LCL300,
Power Factor
Earth Leakage Current • <2 mA at 264 VAC, 60 Hz
Input Protection
3
4.9 W/in LCL500
• LCL150: >489 kHrs,
LCL300: >235 kHrs,
LCL500: >211 kHrs to MIL-HBK-217F at
25 °C, GB
• LCL150: T3.15 A/250 V,
LCL300: T6.3A/250 V,
LCL500: T10A/250 V,
internal fuse fitted in line
Environmental
Operating Temperature • -10 °C to +70 °C, derate from 100% load
Output
Output Voltage
Output Voltage Trim
Initial Set Accuracy
Minimum Load
• See tables
• See tables
at 50 °C to 50% load at 70 °C
• LCL150 convection cooled, LCL300 &
LCL500 have internal fans
Cooling
•
100 mV at 50% load
Operating Humidity
Storage Temperature • -40 °C to +85 °C
Operating Altitude
Vibration
• 5% to 90% non condensing
• None required
• 2 s max for LCL150, 1.5 s max for LCL300,
0.8 s max for LCL500
• 50 ms max for LCL150,
35 ms max for LCL300 & LCL500
Start Up Delay
• 3000 m
• 10-500 Hz, 2 g, 10 mins per cycle on
3 axes
Start Up Rise Time
Hold Up Time
• 10 ms min at 115 VAC and full load
EMC & Safety
Emissions
Line Regulation
•
0.5% max for LCL150,
0.3% for LCL300 & LCL500
• EN55022 level B conducted,
level A radiated
Load Regulation
•
1% max
Transient Response
• 4% max deviation recovery to within 1%
in 500 µs for a 50% load change
• See tables
Harmonic Currents
• EN61000-3-2 class A
LCL150: EN61000-3-2 class C for loads ≥40%
LCL300 & LCL500: EN61000-3-2 class C
for loads ≥20%
Ripple & Noise
Overvoltage Protection • 110-140%, recycle input to reset
Overtemperature
Protection
Overload Protection
Voltage Flicker
ESD Immunity
• EN61000-3-3
• Output turns off when OTP triggered,
measured internally, auto recovery
• 110-150% of rated output power. Delayed
by 1 s min to allow for peak loads.
• EN61000-4-2, 4 kV contact,
8 kV air discharge, Performance Criteria A
Radiated Immunity
EFT/Burst
Surge
• EN61000-4-3, level 2 Perf Criteria A
• EN61000-4-4, level 2 Perf Criteria A
• EN61000-4-5,
installation class 3, Perf Criteria A
• EN61000-4-6, level 2 Perf Criteria A
• EN61000-4-8, 1 A/m Perf Criteria A
• EN61000-4-11, 30% 10 ms, 60% 100 ms,
100% 5000 ms, Perf Criteria A, B, B
Short Circuit Protection • Trip and restart (hiccup mode),
auto recovery
• Fitted to LCL500 only, compensates for
0.25 V max each line
• Fitted on LCL300 & 500 only,
On = logic low or open circuit,
Off = logic high
Remote Sense
Remote On/Off
Conducted Immunity
Magnetic Field
Dips & Interruptions
Safety Approvals
• EN60950-1, UL60950-1, CSA60950
No 22.2