MODEL: L2CE
J: 0 – 5 mA DC (Load resistance 2000 Ω max.)
Power Transducer Series L-UNIT
Z: Specify current (See OUTPUT SPECIFICATIONS)
Voltage
DUAL CT TRANSDUCER
(RMS sensing)
1: 0 – 10 mV DC (Load resistance 10 kΩ min.)
2: 0 – 100 mV DC (Load resistance 100 kΩ min.)
3: 0 – 1 V DC (Load resistance 1000 Ω min.)
4: 0 – 10 V DC (Load resistance 10 kΩ min.)
5: 0 – 5 V DC (Load resistance 5000 Ω min.)
6: 1 – 5 V DC (Load resistance 5000 Ω min.)
0: Specify voltage (See OUTPUT SPECIFICATIONS)
Functions & Features
• Converting an alternating current from a current
transformer into a standard process signal
• Minimum ripple
• 2 transducers housed in one enclosure
• Isolation up to 2000 V AC
• High-density mounting
[3] AUXILIARY POWER SUPPLY
AC Power
B: 100 V AC
C: 110 V AC
D: 115 V AC
F: 120 V AC
G: 200 V AC
H: 220 V AC
J: 240 V AC
DC Power
R: 24 V DC
V: 48 V DC
Typical Applications
• Centralized monitoring and control of motors, pumps or
heaters by DCS
• Monitoring power line and power supply current
75
(2.95)
75
(2.95)
112
(4.41)
[4] OPTIONS
mm (inch)
blank: none
/Q: With options (specify the specification)
MODEL: L2CE–[1][2]–[3][4]
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
ORDERING INFORMATION
• Code number: L2CE–[1][2]-[3][4]
Specify a code from below for each [1] through [4].
(e.g. L2CE-5A-C/Q)
/C02: Polyurethane coating
/C03: Rubber coating
TERMINAL SCREW MATERIAL
/S01: Stainless steel
• Special output range (For codes Z & 0)
• Specify the specification for option code /Q
(e.g. /C01/S01)
GENERAL SPECIFICATIONS
Construction: Stand-alone; terminal access at the front
Connection: M3.5 screw terminals (torque 0.8 N·m)
Screw terminal: Nickel-plated steel (standard) or stainless
steel
[1] INPUT
Current
1: 0 – 1 A AC
5: 0 – 5 A AC
Housing material: Flame-resistant resin (black)
Isolation: Input to output to auxiliary power, between
channels
[2] OUTPUT
Input waveform: Up to 15 % of 3rd harmonic content
Overrange output: 0 to 120 % at 1 – 5 V
Zero adjustment: -5 to +5 % (front)
Current
A: 4 – 20 mA DC (Load resistance 500 Ω max.)
D: 0 – 20 mA DC(Load resistance 500 Ω max.)
E: 0 – 16 mA DC (Load resistance 625 Ω max.)
F: 0 – 10 mA DC (Load resistance 1000 Ω max.)
G: 0 – 1 mA DC (Load resistance 10 kΩ max.)
Span adjustment: 95 to 105 % (front)
http://www.m-system.co.jp/
L2CE SPECIFICATIONS
ES-1962 Rev.2 Page 1/3