L2000 SERIES
Single output
• Load curre nts up to 400A
• 3 phas e or s ingle phas e input
• Shutdown on phas e los s
• 3 phas e powe r factor corre ction
• Single wire curre nt s hare to 5%
• Ide al for N+1 applications
• Curre nt monitor output include d
• UL, CSA, TÜV s afe ty approvals
The L series is a range of single output, high current power supplies ideally suited
to a broad range of applications. Robust performance and field proven reliability
are hallmarks of this series. Field reliability in excess of 100,000 hours has been
documented. The L series will provide stable power for any large electronic
system including telecommunication, data processing and industrial. Typical
applications include broadcast systems, ATM systems and RISC processors and
systems. Semiconductor test equipment, semiconductor and wafer processing
equipment and functional board level testers are other possible applications.
Industrial uses include applications such as laser cutting, water purification,
battery charging, machine control, large scale data logging and optical inspection
equipment. Current sharing, built-in current monitoring, voltage margining and
remote adjustment capability are standard features. Other system interface
features include AC and DC good, OVP, OCP, over temperature protection and
remote enable. Worldwide safety certifications are included.
[ 2 YEAR WARRANTY ]
SPECIFICATION All specifications are typical at nominal input, full load at 25°C unless otherwise stated
OUTPUT SPECIFICATIONS
EMC CHARACTERISTICS
Voltage adjustability
Remote sense
Accessible at front panel
±10%
Radiated noise
EN55022/11, FCC part 15
EN55022/11, FCC part 15
Level A
Level A
Level 3
Level 3
Conducted noise
Open/reverse sense lead protection
Compensates for voltage drop
of up to 0.5V to the load
Electrostatic discharge EN61000-4-2
RF field susceptibility
Electrical fast
transients/bursts
EN61000-4-3
EN61000-4-4
Level 3
Regulation, line or load All outputs, NL to FL
at nominal line or all
±0.2% ; 10mV
Surge susceptibility
EN61000-4-5
Level 3
line variations at FL
GENERAL SPECIFICATIONS
Overshoot/undershoot
None at turn on/off
Hold-up time
Efficiency
230VAC, 2kW load
25ms min.
78%
Transient response
Main output
≤5.0% max. dev.,
≤200µs recovery
to 1.0%
230VAC, full load
25% step load
change at 1A/µs
Isolation voltage
Input/output
Input/chassis
Output/output
3000VAC
1500VAC
500VAC
Temperature coefficient
Ripple and noise
±0.02% /°C
0Hz to 20MHz
50mV pk-pk or 1.0%
Switching frequency
100kHz
Overvoltage protection Reset by cycling AC
115% to 130%
of nominal
Approvals and
standards
TÜV EN60950, UL1950,
CSA C22.2 No. 234/950
Overload protection
105% to 115% full load
Auto recovery
Weight
Size
10kg (22Ibs)
Short circuit protection 90% of rated load
5 x 8 x 11 inches
127 x 203.2 x 279.4 mm
Thermal protection
Current sharing
Auto shutdown, AC reset
50% to 100% load
±5.0%
MTBF
>100,000 hours
Current monitor (V1)
INPUT SPECIFICATIONS
Input voltage range
5VDC at full load
±0.5V
ENVIRONMENTAL SPECIFICATIONS
Thermal performance
Operating ambient
Non-operating
0°C to +50°C
-15°C to +85°C
3 phase
1 phase (optional)
180 to 264VAC
180 to 264VAC
Cooling
45CFM
Internal DC
ball bearing fan
Input frequency range
Input surge current
47Hz to 63Hz
Meets IEEE std. 587.1980;
3kV ring wave
Relative humidity
Altitude
Non-condensing
0% to 95% RH
Operating
Non-operating
6,000 feet max.
55,000 feet max.
Input current
Power factor
208VAC, 3 phase
8A
20A
208VAC, 1 phase
Vibration
5Hz to 500Hz
2.4G rms peak
3 phase
1 phase
0.94
0.65
Power up time
Full load
1.0s max.
PAGE 1