130 Watts
xppower.com
JPS130/JPS130-M Series
•
•
•
•
•
•
•
High Efficiency - up to 90%
Medical Approval (JPS130-M Versions)
3” x 5” Footprint
Zero Voltage Switching Technology
High Power Density
100 W Convection-cooled
Single & Multi Outputs
Specification
Input
General
Input Voltage
Input Frequency
Input Current
Inrush Current
Power Factor
• 90-264 VAC (130-370 VDC)
• 47-63 Hz
Efficiency
Isolation
• Up to 90ꢀ nominal line, full load
• 3000 VAC Input to Output (JPS130),
4000 VAC Input to Output (JPS130-M),
1500 VAC Input to Ground,
• 2.0/1.0 A max at 115/230 VAC
• 30 A at 115 VAC, 60 A at 230 VAC
• 0.9 typical
500 VAC Output to Ground
Switching Frequency
• 120 kHz fixed, 10ꢀ for both active
PFC & PWM
• 6.7 W/In3
Earth Leakage Current • 1.5 mA max at 264 VAC/60 Hz JPS130
250 µA max at 240 VAC/60 Hz JPS130-M
Power Density
MTBF
Input Protection
• Internal 3.15 A/250 V fuse
Both line & neutral fused (JPS130-M)
• 250 kHrs per MIL-HDBK-217F at 25 °C
Environmental
Output
Operating Temperature • 0 °C to +70 °C, (see derating curves)
Cooling
• 130 W with 18 CFM airflow,
100 W with convection cooling
Output Voltage
• See table
Output Voltage Trim
•
10ꢀ on single output models,
Operating Humidity
Storage Temperature
Operating Altitude
• 5-95ꢀ RH, non-condensing
• -20 °C to +85 °C
• 3000 m
5ꢀ on multi output models, other
voltages will track by the same percentage
Initial Set Accuracy
Minimum Load
• At 60ꢀ rated load 1ꢀ single outputs,
3ꢀ on V1 for multi outputs
EMC & Safety
• Single output: no minimum load required
Multi-outputs: (see note 1)
Emissions
• EN55022, level B conducted
FCC 20780, level B conducted
Start Up Rise Time
Hold Up Time
• <20 ms
• 16 ms typical at low line
Harmonic Currents
Voltage Flicker
ESD Immunity
Radiated Immunity
EFT/Burst
• EN61000-3-2
Line Regulation
Load Regulation
•
•
0.5ꢀ Vmin to Vmax
• EN61000-3-3
1ꢀ, 5ꢀ for auxiliaries, 20-100ꢀ
of rated load
• EN61000-4-2, level 3 Perf Criteria A
• EN61000-4-3, 10 V/m Perf Criteria A
• EN61000-4-4, level 3 Perf Criteria A
• EN61000-4-5, level 3 Perf Criteria A
• EN61000-4-6, 3 V Perf Criteria A
Transient Response
Ripple & Noise
• 4ꢀ max deviation, recovery to within
1ꢀ in 500 µs for a 25ꢀ load change
Surge
•
1ꢀ max pk-pk (see note 4)
Conducted Immunity
Dips & Interruptions
Overvoltage Protection • 110-140ꢀ on V1 only,
• EN61000-4-11, 30ꢀ 10 ms, 60ꢀ 100 ms,
95ꢀ 5000 ms Perf Criteria A, B, B
recycle input to reset
Overload Protection
• 110-150ꢀ, auto recovery
Safety Approvals
• JPS130:
EN60950-1:2001, UL60950-1,
CSA C22.2 No. 60950-1,
CE Mark LVD.
Short Circuit Protection • Trip & restart (Hiccup mode)
Temperature
Coefficient
• 0.05ꢀ/°C
JPS130-M: UL2601-1, EN60601-1,
CSA C22.2 No. 601.1
CE Mark LVD.
Remote Sense
• Single output models only, compensates
for up to 0.5 V drop
Fan Output
• 12 V, 450 mA multi-output models only