600W Single Output with PFC Function
HRPG-600 series
Features :
Universal AC input / Full range
Built-in active PFC function, PF>0.95
High efficiency up to 89%
Withstand 300VAC surge input for 5 seconds
Protections: Short circuit / Overload / Over voltage / Over temperature
Built-in cooling fan ON-OFF control
Built-in DC OK signal
Built-in remote ON-OFF control
Standby 5V@0.3A
Built-in remote sense function
No load power consumption<0.75W (Note.7)
Current sharing up to 2400W (3+1) (24V,36V,48V)
5 years warranty
SPECIFICATION
MODEL
HRPG-600-3.3 HRPG-600-5 HRPG-600-7.5 HRPG-600-12 HRPG-600-15 HRPG-600-24 HRPG-600-36 HRPG-600-48
DC VOLTAGE
3.3V
5V
7.5V
12V
15V
24V
36V
48V
RATED CURRENT
CURRENT RANGE
RATED POWER
120A
120A
80A
53A
43A
27A
17.5A
13A
0 ~ 120A
396W
0 ~ 120A
600W
0 ~ 80A
600W
100mVp-p
6.8 ~ 9V
2.0%
0 ~ 53A
636W
120mVp-p
0 ~ 43A
645W
150mVp-p
0 ~ 27A
648W
150mVp-p
0 ~ 17.5A
630W
0 ~ 13A
624W
240mVp-p
RIPPLE & NOISE (max.) Note.2 100mVp-p
VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE Note.3 2.0%
100mVp-p
4.3 ~ 5.8V
2.0%
200mVp-p
OUTPUT
2.8 ~ 3.8V
10.2 ~ 13.8V 13.5 ~ 18V
21.6 ~ 28.8V 28.8 ~ 39.6V 40.8 ~ 55.2V
1.0%
0.3%
0.5%
1.0%
0.3%
0.5%
1.0%
0.2%
0.5%
1.0%
0.2%
0.5%
1.0%
0.2%
0.5%
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
0.5%
1.0%
0.5%
0.5%
1.0%
1.0%
1000ms, 50ms/230VAC
2500ms, 50ms/115VAC at full load
16ms/115VAC at full load
120 ~ 370VDC
16ms/230VAC
Note.5 85 ~ 264VAC
47 ~ 63Hz
VOLTAGE RANGE
FREQUENCY RANGE
POWER FACTOR (Typ.)
EFFICIENCY (Typ.)
PF>0.94/230VAC
PF>0.99/115VAC at full load
86% 88%
INPUT
78.5%
82%
88%
88%
89%
89%
8.5A/115VAC
35A/115VAC
<1.2mA / 240VAC
5A/230VAC
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
70A/230VAC
LEAKAGE CURRENT
105 ~ 135% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed
6 ~ 7V 9.4 ~ 10.9V 14.4 ~ 16.8V 18.8 ~ 21.8V 30 ~ 34.8V
Protection type : Shut down o/p voltage, re-power on to recover
OVERLOAD
41.4 ~ 48.6V 57.6 ~ 67.2V
3.96 ~ 4.62V
OVER VOLTAGE
PROTECTION
80
90
5
(TSW1)detect on heatsink of power transistor
5
(TSW2) detect on heatsink of power doide for 3.3V,5V,7.5V ; 100
5
(TSW2) detect on main power output choke for others
OVER TEMPERATURE
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
5VSB : 5V@0.3A ; tolerance 5%, ripple : 50mVp-p(max.)
PSU turn on : 3.3 ~ 5.6V ; PSU turn off : 0 ~ 1V
5V STANDBY
DC OK SIGNAL
FUNCTION
RC+ / RC-: 4 ~ 10V or open = power on ; 0 ~ 0.8V or short = power off
Load 35 15% or RTH2 50 Fan on
REMOTE CONTROL
FAN CONTROL (Typ.)
WORKING TEMP.
-40 ~ +70 (Refer to output load derating curve)
20 ~ 90% RH non-condensing
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
ENVIRONMENT
-40 ~ +85 , 10 ~ 95% RH
0.03%/ (0 ~ 50
)
10 ~ 500Hz, 5G 10min./1cycle, 60min. each along X, Y, Z axes
UL60950-1, TUV EN60950-1 approved
SAFETY STANDARDS
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
SAFETY &
EMC
(Note 4)
EMI CONDUCTION & RADIATION Compliance to EN55022 (CISPR22) Class B
HARMONIC CURRENT
EMS IMMUNITY
MTBF
Compliance to EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11, ENV50204, EN55024, EN61000-6-2, heavy industry level, criteria A
147.7K hrs min. MIL-HDBK-217F (25
)
OTHERS
NOTE
DIMENSION
PACKING
218*105*63.5mm (L*W*H)
1.58Kg;8pcs/13.6Kg/1.34CUFT
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives. For guidance on how to perform these EMC tests, please refer to EMI testing of component power supplies.
(as available on http://www.meanwell.com)
5. Derating may be needed under low input voltages. Please check the derating curve for more details.
6. Length of set up time is measured at first cold start. Turning ON/OFF the power supply may lead to increase of the set up time.
7. No load power consumption<0.75W when RC+ & RC- (CN100 pin3,4) 0 ~ 8V or short.
File Name:HRPG-600-SPEC 2010-11-29