5秒后页面跳转
HJDL-A26-R PDF预览

HJDL-A26-R

更新时间: 2022-05-14 22:15:07
品牌 Logo 应用领域
爱模 - MSYSTEM /
页数 文件大小 规格书
3页 138K
描述
Space-saving Plug-in Signal Conditioners H-UNIT

HJDL-A26-R 数据手册

 浏览型号HJDL-A26-R的Datasheet PDF文件第2页浏览型号HJDL-A26-R的Datasheet PDF文件第3页 
MODEL: HJDL  
Space-saving Plug-in Signal Conditioners H-UNIT  
LINEARIZATION CODE  
1: Segment data  
2: Square root extraction  
3: Thermocouple  
4: RTD  
DEFAULT  
Linear  
–––  
CURRENT LOOP SUPPLY  
(linearizing; field-programmable)  
Functions & Features  
K
0 – 1000°C  
Pt 100 0 – 100°C  
• Powering a 4 – 20 mA DC current loop  
• Microprocessor based  
• Shortcircuit protection  
INPUT  
Current  
• Applicable to smart transmitters  
• Field-programmable linearization data  
• Loop testing via hand-held programmer PU-2x  
• High-density mounting  
A: 4 – 20 mA DC (Input resistance 250 Ω)  
[1] LINEARIZATION  
0: None  
Typical Applications  
1: Segment data  
2: Square root extraction  
3: Thermocouple  
4: RTD  
• Various 2-wire transmitters  
• Providing isolation and linearization for a 2-wire  
temperature transmitter  
• Linearizing weir flowmeter output to provide a linear-to-  
volume signal  
• Linearizer application  
[2] OUTPUT  
Current  
(4 – 20 mA input)  
• Square root extraction for differential pressure transmitter  
A: 4 – 20 mA DC (Load resistance 600 Ω max.)  
Voltage  
26 (1.02)  
6: 1 – 5 V DC (Load resistance 500 Ω min.)  
93  
(3.66)  
POWER INPUT  
DC Power  
R: 24 V DC  
137  
(5.39)  
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)  
mm (inch)  
[3] OPTIONS  
blank: none  
MODEL: HJDL–A[1][2]–R[3]  
/Q: With options (specify the specification)  
ORDERING INFORMATION  
• Code number: HJDL-A[1][2]-R[3]  
SPECIFICATIONS OF OPTION: Q (multiple selections)  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
Specify a code from below for each of [1] through [3].  
(e.g. HJDL-A1A-R/Q)  
/C02: Polyurethane coating  
Default setting (following table) will be used if not otherwise  
specified.  
/C03: Rubber coating  
TERMINAL SCREW MATERIAL  
/S01: Stainless steel  
No linearization data will be programmed if you don't  
specify type of linearization and required data.  
• Linearization data  
Code 1 segment data: Use Ordering Information Sheet (No.  
ESU-1669) to specify linearization data.  
Code 3 T/C, Code 4 RTD: Specify input sensor type and  
temperature range.  
RELATED PRODUCTS  
• Programming Unit (model: PU-2x)  
• PC configurator software (model: JXCON)  
Downloadable at M-System’s web site.  
• Specify the specification for option code /Q  
(e.g. /C01/S01)  
A dedicated cable is required to connect the module to the  
PC. Please refer to the internet software download site or  
the users manual for the PC configurator for applicable  
HJDL SPECIFICATIONS  
ES-3474 Rev.9 Page 1/3  
http://www.m-system.co.jp/  

与HJDL-A26-R相关器件

型号 品牌 描述 获取价格 数据表
HJDL-A26-R/Q MSYSTEM Space-saving Plug-in Signal Conditioners H-UNIT

获取价格

HJDL-A2A-R MSYSTEM Space-saving Plug-in Signal Conditioners H-UNIT

获取价格

HJDL-A2A-R/Q MSYSTEM Space-saving Plug-in Signal Conditioners H-UNIT

获取价格

HJDL-A36-R MSYSTEM Space-saving Plug-in Signal Conditioners H-UNIT

获取价格

HJDL-A36-R/Q MSYSTEM Space-saving Plug-in Signal Conditioners H-UNIT

获取价格

HJDL-A3A-R MSYSTEM Space-saving Plug-in Signal Conditioners H-UNIT

获取价格