Current and Voltage Controls
3-Phase Max. and Min. Current Control
Type H 475
• 3-phased current metering relay
• Measures on current with 3-phased current
metering transformers, type A74-.. ...
• Measures if all 3-phase currents are within
set limits
• Upper and lower limits separately adjustable
• Output: 10 A SPDT relay
• For mounting on DIN-rail in accordance with
DIN/EN 50 022
• H4-housing
• LED-indication for power supply and output ON
• AC power supply 2-phases
Product Description
3-phase current metering re- tion such as a large mixer has Housing
lay with separate setting of to be kept within a set current Type
upper and lower current level. value in order not to overload Output
For DIN-rail mounting. Often the system.
used where a certain applica-
Ordering Key
H 475 156 230
Power supply
Type Selection
Plug
Output
Supply: 115 VAC
H 475 156 115
Supply: 230 VAC
H 475 156 230
Supply: 400 VAC
H 475 156 400
Screw
terminals
SPDT
Output Specifications
Input Specifications
Input from current
transformers
Terminal 5
Terminal 6
Terminal 7
Output
SPDT relay
250 VAC (rms)
(cont./elect.)
A74-.. ...
Rated insulation voltage
red, phase L1
white, phase L2
yellow, phase L3
black
Contact ratings (AgCdO)
Resistive loads
µ (micro gap)
AC 1
DC 1
or
10 A/250 VAC (2500 VA)
1 A/250 VDC (250 W)
10 A/25 VDC (250 W)
2.5 A/230 VAC
Terminal 8
Input voltage
0.4-4 Vp
Small inductive loads AC 15
DC 13
5 A/24 VDC
Mechanical life
Electrical life
≥ 30 x 106 operations
≥ 2.5 x 105 operations
Supply Specifications
AC 1
(at max. load)
Power supply AC types
Rated operational voltage
Through term. 22 & 24 115
230
Overvoltage cat. III (IEC 60664)
(IEC 60038)
115 VAC ±15%, 45 to 65 Hz
230 VAC ± 15%, 45 to 65 Hz
400 VAC ± 15%, 45 to 65 Hz
≤ 40 ms
Operating frequency
Dielectric strength
Dielectric voltage
Rated impulse withstand volt. 4 kV (1.2/50 µs) (cont./elect.)
(IEC 60664)
≤ 7200 operations/h
≥ 2 kVAC (rms) (cont./elect.)
400
Voltage interruption
Dielectric voltage
2 kVAC (rms) (supply/elect.)
Rated impulse withstand volt. 4 kV (1.2/50 µs) (line/neutral)
(line/line), no direct connec-
tion to electronics
Rated operational power
2.5 VA
Specifications are subject to change without notice (26.10.99)