GPC225 Commercial/GPM225 Medical
225 Watt Global Performance Switchers
FEATURES:
• Wide-range ac input 85-264 Vac
• 2-year warranty
• Conducted EMI exceeds FCC Class B and CISPR 22
Class B (Commercial models) and CISPR 11 Class B
(Medical models)
• Commercial Approved to UL1950, IEC950 and
CSA22.2-234 L3
• Medical Approved to UL2601-1, IEC601-1 and
CSA22.2 No. 601
marked to LVD
•
SPECIFICATIONS:
Ac Input
85-264 Vac, 47-63 Hz single phase.
line impedance and distortion. Other settings are avail-
able to the user through adjustment of built-in potentiometer.
Input Current
Maximum input current at 120 Vac, 60 Hz with full rated
output load: 5.5 A
Output Noise
0.5% rms, 1% pk-pk, 20 MHz bandwidth, differential
mode. Measured with noise probe directly across output
terminals of the power supply.
Hold-UpTime
20 ms minimum from loss of ac input at full load, nominal
line (115 Vac).
Transient Response
500 µs typical response time for return to within 0.5% of
final value for a 50% load step change. ∆i/∆t<0.2 A/µs.
Maximum voltage deviation is 3.5%. Startup/shutdown
overshoot less than 3%.
Output Power
175 W convection; 225 W with 26 cfm air; 250 W peak. Peak
ratings are for 60 s maximum duration, 10% duty cycle.
Overload Protection
Remote Sense
Fully protected against short circuit and output overload.
Short circuit protection is cycling type power limit.
Recovery after fault is automatic. Factory set to begin
power limiting at approximately 250 W.
Provided as a standard feature.
Voltage Adjustment
Built-in potentiometer adjusts voltage ±5%.
Overvoltage Protection
EMI/EMC Compliance
124% ± 12% typical.
All models include built-in EMI filtering to meet the
following emissions requirements:
Efficiency
EMI SPECIFICATIONS
Conducted Emissions GPC225 EN55022 Class B; FCC Class B
Conducted Emissions GPM225 EN55011 Class B; FCC Class B
COMPLIANCE LEVEL
70% at full rated load, nominal input voltage, depending
on model and load distribution.
Static Discharge
EN61000-4-2, 6 kV contact, 8 kV air
EN61000-4-3, 3 V/meter
EN61000-4-4, 2 kV, 5 kHz
Input Protection
Internal ac fuse provided. Designed to blow only if a
catastrophic failure occurs in the unit.
RF Field Susceptibility
Fast Transients/Bursts
Surge Susceptibility
EN61000-4-5, 1 kV diff., 2 kV com.
Inrush Current
Inrush is limited by internal thermistors. Inrush at 240 Vac
under cold start conditions will not exceed 60 A.
Commercial Leakage Current
0.95 mA 254 Vac @ 60 Hz input (with no deviations).
Commercial Safety
Temperature Coefficient
Approved to UL1950, CSA22.2 No. 234 Level 3, IEC950,
EN60950 and CISPR22. UL file #E135803 commercial;
CSA #LR46516. The output(s) are intended for safety
earthed Signal Output and Intermediate Circuits only. All
dc outputs are SELV under normal and single fault
conditions.
0.03%/°C typical on all outputs.
Thermal Shutdown
Provided as a standard feature. Designed to protect unit
from prolonged over temperature.
Environmental
Medical Leakage Current
Designed for 0 to 50°C operation at full rated output
power; derate output current and total output power by
2.5% per °C above 50°C. See Environmental and
Packaging Specifications on next page.
60 µA. 254 Vac @ 60Hz input.
Medical Safety
Approved to UL2601, CSA22.2 No. 601 Level 3 and
IEC601. UL file E116994; CSA #LR46516. The output(s)
are intended for safety earthed Signal Output and
Intermediate Circuits only. The output(s) are not accept-
able for patient connection without additional isolation. All
dc outputs are SELV under normal and single fault
conditions.
Power Fail
TTL- or CMOS-compatible output goes low (< 0.5 V) 5 ms
before output voltage drops more than 4% below nominal
voltage upon loss of ac power. The signal is factory set to
trip on 84 to 94 Vac brown-out depending upon incoming