5秒后页面跳转
GLQ PDF预览

GLQ

更新时间: 2024-11-30 01:25:55
品牌 Logo 应用领域
库柏 - COOPER /
页数 文件大小 规格书
1页 36K
描述
Specialty Fuse Fast-Acting, Size Rejecting

GLQ 数据手册

  
®
Bu s s m a n n  
S p e c ia lt y Fu s e  
Fa s t -Ac t in g , S ize Re je c t in g  
GLQ  
& HLQ  
Dim e ns iona l Da ta  
FUSE  
0.63"  
(15.9mm)  
FUSE AND CARRIER  
Ca ta log Sym bol: GLQ (Fuse) HLQ (Fuseholder)  
Fa s t-Ac ting Re je c tion Style  
Am pe re Ra ting: 1-10 Amperes  
Volta ge Ra ting: 300 Volts AC or less  
Inte rrupting Ra ting: 10,000 Amperes  
Age nc y Inform a tion:  
2.250''  
57.15mm  
.850''  
21.59mm  
.720''  
18.29mm  
Line Lead  
Load Lead  
.850''  
21.59mm  
C
L
Fus e :  
UL Listed, Std. 248-14, Guide JDYX, File E19180  
CSA Certified, C22.2 No. 248.14, Class 1422-01, File 53787  
Fus e holde r:  
UL Recognized, Guide IZLT2, File E14853  
CSA Certified, Class 6225-01, File 47235  
MOUNTING HOLE  
.870''  
.255''  
6.48mm  
22.10mm  
.635''  
16.13mm  
.740''  
18.80mm  
.410''  
Ge ne ra l Inform a tion:  
10.41mm  
Knockout Hole  
Keyhole Punch  
• Size of GLQ fuse varies with ampere rating.  
• GLQ fuses mount in HLQ size rejecting carriers (prevents  
overfusing).  
• Fuse and knob are an integral one-piece unit. There are no  
replacement knobs (caps).  
Tim e -Curre nt Cha ra c te ris tic Curve s Ave ra ge Me lt  
AMPERE  
RATING  
100  
• HLQ carrier comes with 6∑ of #18 red insulated solid copper  
wire attached to the line side.  
• Customer inserts a #18 insulated solid copper wire into load  
side receptacle.  
• Units can be panel mounted with a separate steel clip. For  
the knockout hole (see above), choose #BK/A-104. For the  
keyhole punch type hole, choose #6374 for panels .043” to  
.062” thick, or #4909 for panels .030” to .042” thick.  
• Do not put tension on line (rear) terminal of fuse-holder.  
10  
1
Ele c tric a l Ra tings for Type GLQ Fus e s a nd Re je c tion  
Style Ca rrie rs  
Fuse  
Carrier  
Fuse  
Carrier  
HLQ-3¤Ω¡º  
HLQ-5  
GLQ-1  
HLQ-1flΩ¡º  
HLQ-1flΩ¡º  
HLQ-1flΩ¡º  
HLQ-3¤Ω¡º  
HLQ-3¤Ω¡º  
GLQ-3  
GLQ-4  
GLQ-5  
GLQ-9  
GLQ-10  
GLQ-1⁄Ω™  
GLQ-1flΩ¡º  
GLQ-2  
.1  
HLQ-5  
HLQ-10  
HLQ-10  
GLQ-2⁄Ω™  
CE logo denotes compliance with European Union Low Voltage Directive  
(50-1000 Vac, 75-1500 Vdc). Refer to Data Sheet: 8002 or contact  
Bussmann Application Engineering at 636-527-1270 for more information.  
.01  
CURRENT IN AMPERES  
The only controlled copy of this Data Sheet is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is  
intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change  
design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information con-  
tained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.  
Form No. GLQ & HLQ  
Page 1 of 1  
5-22-02  
SB02233  
Data Sheet: 2033