GLD140 GOLD PERFORMANCE SWITCHERS
FEATURES:
• Compact size (4.5" x 8.5" x 1.95")
• Power factor corrected to IEC 1000-3-2 Class A
• Documented FMEA, WCA and EMC test results
• Meets EMC directive
• EMI compliance to CISPR11, FCC Class B, IEC601-1-2
• Approved to UL2601, IEC601-1 and
CSA 22.2 No. 601.1-M90 and EN60601: 1990
marked to LVD
•
Temperature Coefficient
0.03%/ºC typical on all outputs.
SPECIFICATIONS (PRELIMINARY):
AC Input
80-270Vac, 47-63Hz single phase.
Environmental
Designed for 0 to 50°C operation at full rated output power; derate
output current and total output power by 2.5% per °C above 50°C. See
Environmental and Packaging Specifications (p. 11) for additional
information.
Input Current
Active input circuitry ensures compliance with IEC1000-3-2, Class A.
Maximum input current at minimum input and full load is 3.0A.
Thermal Shutdown
Inrush Current
Provided as a standard feature to protect unit from prolonged
overtemperature.
Inrush is limited by internal thermistors. Inrush at 240Vac, averaged over
first AC half-cycle under cold start conditions, will not exceed 37A.
Worst-case current under hot start conditions will be 60A (assumes 2-
sec. delay for power-on).
Fan Output
An additional 12VDC, 250mA output suitable for powering a DC fan is
included in all models ( Factory installed cover with fan makes this output
unavailable). The output is protected by an internal PTC in the event of an
overload.
Input Protection
Internal AC fuse provided on all units.
Holdup Time
25ms minimum from loss of AC input at full load.
Overshoot
Less than 2% overshoot at turn-on under nominal conditions, inversely
proportional to input voltage and temperature. Less than 2% overshoot at
turn-off under all conditions.
Inhibit
Inhibit signal is pulled to the V1 output common to reduce average output
voltage to less than 5% of nominal.
Turn-on Time
Power Fail
Less than 1.2s at 115Vac, 25ºC (inversely proportionate to input voltage
and thermistor temperature).
TTL/CMOS compatible output goes low (<0.5V) 8ms before output
voltage drops more than 4% below nominal upon loss of AC power.
EMI/EMC Compliance
All models include built-in EMI filtering to meet the following emissions
requirements:
Power Good
TTL/CMOS compatible output goes high more than 100ms after V1
reaches undervoltage threshold, and should ensure that sufficient energy
is stored in the input section to provide normal power fail/ shutdown.
EMI SPECIFICATIONS
Conducted Emissions
Static Discharge
RF Field Susceptibility
Fast Transients/Bursts
Surge Susceptibility
COMPLIANCE LEVEL
EN55011 Class B; FCC Class B
EN61000-4-2, 6 kV contact, 8 kV air
EN61000-4-3, 3 V/meter
EN61000-4-4, 2 kV, 5 kHz
EN61000-4-5, 1 kV diff., 2 kV com.
Efficiency
70% minimum depending upon model.
Output Power
Continuous rating is 130W with unrestricted natural convection, or 150W
with forced convection. All models capable of 110% of rated power for
60 sec., 10% duty cycle maximum.
Leakage Current
50µ under normal conditions (132Vac @ 60Hz). Maximum under single-
fault conditions (254Vac @ 50Hz) is 90µA. Patient sink leakage with
120Vac, 60Hz applied to any output is less than 500µA.
Remote Sense
Provided as a standard feature.
Overload Protection
Fully protected against short circuit and output overload. Short circuit
protection is cycling type power limit.
Design Verification
Condor Gold Series power supplies have undergone rigorous review and
design analysis. The following documentation is available upon request:
Output Noise
1. Failure Mode and Effects Analysis (FMEA)
2. MTBF study
3. Worst Case Analysis of output performance and signals
4. DVT data
0.5% RMS, 1% Pk-Pk, 20MHz Bandwidth, differential mode. Measured
with noise probe directly across output terminals of the power supply.
Voltage Adjustment
Factory set to specified voltage and tolerance with user adjustable
potentiometer. User can adjust at least ±5% of nominal output voltage.
Consult factory for application assistance.
5. EMC/susceptibility test results
Condor D.C. Power Supplies, Inc./A subsidiary of SL Industries, Inc.
2311 Statham Parkway, Oxnard, CA 93033 800-235-5929 805-486-4565 FAX 805-487-8911 • www.condorpower.com/
•
•
•
110