FXP6000 AC-DC Series Data Sheet
Features
• Three-phase AC input
• Suitable for 3U or 5U height mounting
• Single-wire current share or Droop current share
• Remote voltage adjust and current monitoring
• Overtemperature, overload, and overvoltage protection
• LED supply status indicators
• Current-share control for up to 30 units
• Standard & customized rack adaptors available
• Front panel selectable-input-range model availability
• (For higher power requirements, see FXP7000)
• (For chassis-mount requirements, see FXC6000 OR FXC7000)
FXP6000 Front and Rear Views
Description
The FXP6000 Series of rack-mounted power systems provides AC front-end capability to automatic test equipment,
telecom, data communications, and other distributed power designs. The FXP systems may be paralleled up to 180 kW
of output power. The FXP family is hot pluggable and includes paralleling (OR-ing) diodes. These power supplies
provide excellent protection against input voltage transients.
The FXP family power supplies may be plugged into or removed from an operating system when used in a redundant
power configuration. Access to interfaces for remote sensing, remote voltage adjust, current sharing, current
monitoring, power supply status, standby voltage and inhibit, as well as power connections, is through a connector at
the rear of the supply. The FXP has its fan, handles, voltage adjust, and indicator lights on the front panel and a single
hot-plug connector on the rear. Airflow is from the front through the rear. Alarm, monitoring, and control signals are
floating from the main output and can be referenced to the positive or negative output or sense line of the power supply.
The output is floating with respect to the chassis and may be used as a positive or negative polarity supply.
The FXP6000 Series meets international safety requirements and is CE Marked to the Low Voltage Directive. This
series operates on three-phase European voltages as well as (up to) 480VAC, delta or wye.
Hot-Pluggable Model Selections
OUTPUT
VOLTAGE
INPUT VOLTAGE RANGE
3-PHASE (VAC)
ADJUSTMENT
RANGE
MAXIMUM OUTPUT
CURRENT
LINE
REGULATION
LOAD
INITIAL SETTING
ACCURACY
MODEL
REGULATION (NOTE 1)
FXP6000-32-S (NOTE 2) 32V
FXP6000-48-S (NOTE 2) 48V
180 to 264 or 342 to 528
180 to 264 or 342 to 528
30.5 to 33.5V
45.6V to 50.4V
175A
125A
0.2%
0.2%
0.2%
31.93V to 32.07V
47.90V to 48.10V
0.15%
NOTES: 1) With Remote Sense connected.
2) User-selectable input voltage ranges.
Input Specifications
PARAMETER
DESCRIPTION/CONDITIONS
MIN
NOM
MAX
UNITS
Input Voltage - AC
3-phase delta low input range, nominal.
3-phase delta high input range, nominal.
Continuous deviation from the above nominals.
200
380
-10
240
480
+10
VAC
%
Input Current
Inrush Surge Current
Per phase at full rated load.
Internally limited.
FXP6000 at 180 VAC:
Vin = 264VAC (one cycle). 25° C:
Vin = 528VAC (one cycle). 25° C:
28
38
38
ARMS
APK
Input Frequency
Hold-up Time
AC input.
After last AC line peak at full power.
50
20
20
60
Hz
208 VAC:
410 VAC:
ms
Operating Frequency
Power Factor
Switching frequency, fixed.
100
kHz
W/VA
0.90
FEB 11, 2005 revised to JAN 09, 2007
Page 1 of 8