Bus s m a nn
Fus e tron®
FRS-R
6 5 -6 0 0 A
Dua l-Ele m e nt, Tim e -De la y Fus e s
Cla s s RK5 –– 6 0 0 Volt
Dim e ns iona l Da ta
A
B
Dim e ns ions (inches)
Ampere Ratings
65-100
110-200
225-400
A
B
7.88 (± 0.062)
9.63 (± 0.062)
11.63 (± 0.094)
13.38 (± 0.094)
1.11 (± 0.020)
1.61 (± 0.020)
2.34 (± 0.020)
2.88 (± 0.020)
450-600
Ca ta log Sym bol: FRS-R
Ge ne ra l Inform a tion:
Dual-Element, Time-Delay – 10 seconds (minimum) at 500%
• Provides motor overload, ground fault and short-circuit
protection. When used in circuits subject to surge currents
such as those caused by motors, transformers and other
inductive components, these fuses can be sized close to
full-load amperes to give maximum overcurrent protection.
• The time-delay feature makes it possible to use fuse ampere
ratings which are much smaller than those of non-time-delay
fuses. Considerable cost saving occurs by permitting the use
of smaller size switches, panels and fuses themselves.
• Provides a good degree of short-circuit protection (greater
current-limitation) to help protect downstream components
from high fault currents.
• Gives motor running back-up protection to motors without
extra costs.
• Helps protect motors against burnout from overloads and
single phasing when sized properly.
• Simplifies and improves blackout prevention (selective
coordination ratios).
• Dual-element fuses can be applied in circuits subject to
temporary motor overloads and surge currents to provide
both high-performance, short-circuit and overload protection.
rated current
Current-Limiting
Am pe re Ra ting: 65 to 600 Amperes
Volta ge Ra ting: 600 Volts AC (or less)
Inte rrupting Ra ting: 200,000A RMS Sym.
DC Ratings (20,000AIC @ 300 Vdc)
†
Age nc y Approva ls :
U.L. Listed, Std. 248-12, Class RK5, Guide JDDZ, File E4273
CSA Certified, C22.2 No. 248.12, Class 1422-01, File 53787
Ca ta log Num be rs
FRS-R-65
FRS-R-70
FRS-R-75
FRS-R-80
FRS-R-85
FRS-R-90
FRS-R-100
FRS-R-110
FRS-R-125
FRS-R-135
FRS-R-150
FRS-R-175
FRS-R-200
FRS-R-225
FRS-R-250
FRS-R-275
FRS-R-300
FRS-R-325
FRS-R-350
FRS-R-400
FRS-R-450
FRS-R-500
FRS-R-600
—
Ca rton Qua ntity a nd We ight
Weight*
Ampere
Ratings
Carton
Qty.
Lbs.
0.54
1.22
3.00
5.00
Kg.
65–100
1
1
1
1
0.245
0.544
1.359
2.268
101–200
201–400
401–600
*Weight per carton.
Fus e Re duc e rs For Cla s s R Fus e s
Fus e bloc ks – Cla s s R Ca ta log Num be rs
(Clip Re ta ining Spring Sta nda rd, Suffix “R”)
Desired
Fuse (Case)
Size
Catalog Number
(Pairs)
Equipment
Fuse Clips
Terminal Type (Suffix No.)
Box Lug w/
600V
Basic
200A
100A
100A
200A
100A
200A
400A
No. 2621-R
No. 2641-R
No. 642-R
Catalog
Number
R60100-1
—
Reinforced Clip
CU only
Amps
Poles
400A
65
1
CR
CR
CR
CR
CR
CR
COR
No. 2661-R
No. 2662-R
No. 2664-R*
to
2
3
1
1
1
R60100-2
R60100-3
R60200-1
R60400-1
R60600-1
COR
COR
—
600A
100
to 200
to 400
to 600
*Single reducer only (pair not required).
For additional information, see BIF Document 1118.
—
—
For additional information on the R600 Series fuseblocks, refer to
BIF Document 1111.
CE logo denotes compliance with European Union Low Voltage Directive
(50-1000 Vac, 75-1500 Vdc). Refer to BIF document #8002 or contact
Bussmann Application Engineering at 636-527-1270 for more information.
† To obtain information for 0-60 Amps, access BIF # 1017
Form No. FRS-R 70-600
Page 1 of 3
A00115
11-1-00
BIF Doc #1018