5秒后页面跳转
FN9264XX-1-06-Y PDF预览

FN9264XX-1-06-Y

更新时间: 2024-11-19 02:50:27
品牌 Logo 应用领域
夏弗纳 - Schaffner /
页数 文件大小 规格书
6页 2293K
描述
General Purpose Power Entry Module with Switch

FN9264XX-1-06-Y 数据手册

 浏览型号FN9264XX-1-06-Y的Datasheet PDF文件第2页浏览型号FN9264XX-1-06-Y的Datasheet PDF文件第3页浏览型号FN9264XX-1-06-Y的Datasheet PDF文件第4页浏览型号FN9264XX-1-06-Y的Datasheet PDF文件第5页浏览型号FN9264XX-1-06-Y的Datasheet PDF文件第6页 
IEC Inlet Filters FN 9264  
DATASHEET  
General Purpose Power Entry Module with Switch  
Rated currents up to 10 A  
Approvals  
High quality 2-pole rocker switch  
Optional reduced leakage current versions (A/B  
type)  
Complies with IEC/EN 60601-1  
Snap-in versions (S type)  
Good attenuation performance  
Features and benefits  
Excellent conducted attenuation performance,  
based on chokes with high saturation resistance  
and good thermal behavior  
Performance indicators  
High quality 2-pole rocker switch for all-pole  
disconnection  
Faston terminals for easy assembly  
FN 9264 B versions comply with the requirements of  
1MOP acc. to IEC/EN 60601-1 for creepage and  
clearance, leakage current and high potential  
testing  
As flange mount and snap-in types available  
Typical applications  
Portable electrical and electronic equipment  
EDP and office equipment  
Technical specifications  
Single-phase power supplies  
250 VAC, 50/60 Hz  
DC to 400 Hz  
Maximum continuous operating voltage  
Operating frequency  
Switch-mode power supplies  
Test and measurement equipment  
1 to 10 A @ 40°C max.  
Rated currents  
P –> PE 2000 VAC for 2 sec (Standard)  
P –> PE 2500 VAC for 2 sec (B-types)  
P –> N 760 VAC for 2 sec  
Medical electrical devices (MD) and In-Vitro  
Diagnostic (IVD) medical devices  
High potential test voltage for capacitors  
IP 40 according to IEC 60529  
Protection category  
Typical electrical schematic  
-25°C to +85°C (25/85/21)  
-25°C to +85°C (25/85/21)  
Temperature range (operation and storage)  
UL 60939-3, CSA Std C22.2 No. 8, IEC/EN 60939-3, GB/  
T15287, GB/T15288  
Design corresponding to  
UL 94 V-2 or better  
≥ 616,000 hours  
Flammability corresponding to  
MTBF @ 40°C/230 V (Mil-HB-217F)  
Rocker switch description  
Function  
2-pole, dark not illuminated  
Marking I – 0  
Inrush current 100 A  
Electrical specifications  
50,000 on-off operations for 10 A according to EN  
610581-1  
Switch ratings  
Europe (ENEC)  
10 A (4 A), 250 VAC* 5E4  
16 A (4 A), 250 VAC* 1E4  
20 A, 125 VAC 1 HP; 250 VAC 2 HP;  
USA (UL)  
* Value in () relates to the inductive current charge: cosφ = 0.65  

与FN9264XX-1-06-Y相关器件

型号 品牌 获取价格 描述 数据表
FN9264XX-2-06-Y Schaffner

获取价格

General Purpose Power Entry Module with Switch
FN9264XX-3-06-Y Schaffner

获取价格

General Purpose Power Entry Module with Switch
FN9264XX-4-06-Y Schaffner

获取价格

General Purpose Power Entry Module with Switch
FN9264XX-6-06-Y Schaffner

获取价格

General Purpose Power Entry Module with Switch
FN9266-10-06 Schaffner

获取价格

High Performance Power Entry Module with Switch
FN9266-1-06 Schaffner

获取价格

High Performance Power Entry Module with Switch
FN9266-2-06 Schaffner

获取价格

High Performance Power Entry Module with Switch
FN9266-4-06 Schaffner

获取价格

High Performance Power Entry Module with Switch
FN9266-6-06 Schaffner

获取价格

High Performance Power Entry Module with Switch
FN9266A-10-06 Schaffner

获取价格

High Performance Power Entry Module with Switch