MODEL: FJDL
Space-saving Plug-in Signal Conditioners F-UNIT
LINEARIZATION CODE
1: Segment data
2: Square root extraction
3: Thermocouple
4: RTD
DEFAULT
Linear
–––
CURRENT LOOP SUPPLY
(linearizing; field-programmable)
Functions & Features
K
0 – 1000°C
Pt 100 0 – 100°C
• Powering a 4 – 20 mA DC current loop
• Microprocessor based
• Shortcircuit protection
INPUT
Current
• Applicable to smart transmitters
• Field-programmable linearization data
• Loop testing via hand-held programmer PU-2x
• High-density mounting
A: 4 – 20 mA DC (Input resistance 250 Ω)
[1] LINEARIZATION
0: None
Typical Applications
1: Segment data
2: Square root extraction
3: Thermocouple
4: RTD
• Various 2-wire transmitters
• Providing isolation and linearization for a 2-wire
temperature transmitter
• Linearizing weir flowmeter output to provide a linear-to-
volume signal
• Linearizer application
[2] OUTPUT
Current
(4 – 20 mA input)
• Square root extraction for differential pressure transmitter
A: 4 – 20 mA DC (Load resistance 600 Ω max.)
Voltage
26 (1.02)
6: 1 – 5 V DC (Load resistance 500 Ω min.)
[3] POWER INPUT
100
(3.94)
AC Power
K: 85 – 132 V AC
(Operational voltage range 85 – 132 V, 47 – 66 Hz)
L: 170 – 264 V AC
137
(5.39)
mm (inch)
(Operational voltage range 170 – 264 V, 47 – 66 Hz)
DC Power
R: 24 V DC
MODEL: FJDL–A[1][2]–[3][4]
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
P: 110 V DC
(Operational voltage range 85 – 150 V, ripple 10 %p-p max.)
ORDERING INFORMATION
• Code number: FJDL-A[1][2]-[3][4]
Specify a code from below for each of [1] through [4].
(e.g. FJDL-A1A-R/Q)
[4] OPTIONS
blank: none
Default setting (following table) will be used if not otherwise
specified.
/Q: With options (specify the specification)
No linearization data will be programmed if you don't
specify type of linearization and required data.
• Linearization data
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
Code 1 segment data: Use Ordering Information Sheet (No.
ESU-1669) to specify linearization data.
Code 3 T/C, Code 4 RTD: Specify input sensor type and
temperature range.
/C02: Polyurethane coating
/C03: Rubber coating
TERMINAL SCREW MATERIAL
/S01: Stainless steel
• Specify the specification for option code /Q
(e.g. /C01/S01)
FJDL SPECIFICATIONS
ES-1474 Rev.12 Page 1/3
http://www.m-system.co.jp/