DIN Rail Mount Contactor
Datasheet
DRA3P Series
• 2.4 & 4.2 Amp rated Solid State Contactor
• Load voltage range of 48-510 VAC, 3-Phase
• Fits standard 35mm DIN-RAIL
• LED input status indicator
• AC or DC control
• Zero-crossing (resistive loads) or instantaneous turn-on (inductive loads) output
• cUL Recognized, IEC Rated, CE & RoHS Compliant, Horsepower Rated
• Built in Overvoltage Protection
Start / Stop
PRODUCT SELECTION
Control Voltage
4-6 VDC Control
18-28 VDC Control
36-60 VAC Control
90-140 VAC Control
200-265 VAC Control
2.4 A
4.2 A
DRA3P48D2
DRA3P48E2
DRA3P48C2
DRA3P48B2
DRA3P48A2
DRA3P48D4
DRA3P48E4
DRA3P48C4
DRA3P48B4
DRA3P48A4
AVAILABLE OPTIONS
Rated Load Current
2: 2.4 Amp/
1HP @ 480 VAC
4: 4.2 Amp/
Controlled Legs
Blank: 3 Legs
2: 2 Legs
Operating Voltage
48: 48-510 VAC
2HP @ 480 VAC
Series
DRA 3P 48
D
4
R
2
Function
Control Voltage
Switching Type
3P: 3 Phase
D: 4-6 VDC
Blank: Zero Voltage Turn-On
R: Instantaneous Turn-On
E: 18-28 VDC
A: 200-265 VAC
B: 90-140 VAC
C: 36-60 VAC
Required for valid part number
For options only and not required for valid part number
OUTPUT SPECIFICATIONS AC Output (1)
Description
Operating Voltage (47-63Hz) [Vrms]
2.4 A
48-510
480
4.2 A
48-510
480
Rated Operating Voltage (Vrms)
Transient Overvoltage [Vpk] (2)
1200
2.4/2.4
2.1/2.1
0.15
1200
4.2/2.4
3.4/2.1
0.15
Maximum Resistive Load Current UL/AC51 [Arms] (3, 8)
Maximum Motor Load Current UL/AC53 [Arms] (3, 4)
Minimum Load Current [Arms]
Maximum Off-State Leakage Current @ Rated Voltage [mArms]
Minimum Off-State dv/dt @ Maximum Rated Voltage [V/µsec]
Maximum On-State Voltage Drop @ Rated Current [Vrms]
Maximum Surge Current (50/60 Hz, 1 cycle) [Apk]
Maximum I²t for Fusing (50/60 HZ, 1/2 cycle) [A² sec]
1.0
500
1.0
500
1.15 per Channel
285/300
410/375
0.5/0.37
1.0/0.75
1.0/0.75
0.5
24/10
0.5-4.0
12.0 in lb (1.36 Nm)
1.15 per Channel
285/300
410/375
0.75/0.37
1.5/0.75
2.0/0.75
0.5
(5)
(6)
(7)
HP/IEC 60947 Rating @ 240V, 40°C [HP/KW]
HP/IEC 60947 Rating @ 380V, 40°C [HP/KW]
HP/IEC 60947 Rating @ 480V, 40°C [HP/KW]
Minimum Power Factor (with Maximum Load)
Min/Max stranded/solid wire [AWG]
Min/Max stranded/solid wire [IEC mm²]
Load Terminal Screw Torque Range:
24/10
0.5-4.0
12.0 in lb (1.36 Nm)
FDE-07-01 REV. A
Do not forget to visit us at: www.crydom.com