DIN Rail Mount
Datasheet
DR22 Series
AC Output DIN Rail Mount SSRs
• Output ratings up to 35 Amps at 600 VAC
• Built-in overvoltage protection
• Relay or Contactor configuration
• Integral heat sink eliminates the need for complex thermal calculations
• DBC substrate for superior thermal performance
• "Elevator" screw option to allow the use of ring or lug type terminals
• IP20 touch-safe housing
• AC or DC control
• C-UL-US and TUV approved
PRODUCT SELECTION
Control Voltage
90-280 VAC/VDC
4-32 VDC
20A
DR2260A20x
DR2260D20x
30A
DR2260A30x
DR2260D30x
35A
DR2260A35x
DR2260D35x
AVAILABLE OPTIONS
Rated Load Current
20: 20 Amps
Switching Type
Blank: Zero Voltage Turn-On
R: Instantaneous Turn-On
(Motor Rating Certified)
30: 30 Amps
Operating Voltage
60: 48-600 VAC
35: 35 Amps [High I2t]
Series
DR22
60
A
20
UV
R
J
Control Voltage (1)
Terminal Layout
U: Relay Configuration
V: Contactor Configuration J: Spring Terminal
Input Connector
A: 90-280 VAC/VDC
D: 4-32 VDC
Blank: Screw Terminal
(std. screw)
(V and W suffixes only)
W: Contactor Configuration
(elevator screw)
Required for valid part number
For options only and not required for valid part number
OUTPUT SPECIFICATIONS (2)
Description
Operating Voltage (47-440Hz) [VRMS]
20A
48-600
1200
30A
48-600
1200
35A
48-600
1200
Transient Overvoltage [Vpk] (3)
Maximum Off-State Leakage Current @ Rated Voltage [mARMS]
Minimum Off-State dV/dt @ Maximum Rated Voltage [V/μsec]
Load Current, General Use UL508/LC A IEC62314 @ 40°C [ARMS]
Load Current, Motor Starting UL508 FLA/LC B IEC62314 @ 40°C [ARMS]
Minimum Load Current [mARMS]
1
500
20
8.5/4.8
100
1
500
30
14/7.6
100
1
500
35
26/14
150
Maximum 1 Cycle Surge Current (50/60Hz) [Apk]
Maximum On-State Voltage Drop @ Rated Current [Vpk]
Maximum 1/2 Cycle I² t for Fusing (50/60Hz) [A² sec]
Minimum Power Factor (at Maximum Load) (4)
Motor Rating UL 508/IEC62314 [HP (kW)]: 120 VAC
Motor Rating UL 508/IEC62314 [HP (kW)]: 240 VAC
Motor Rating UL 508/IEC62314 [HP (kW)]: 480 VAC
286/300
1.35
409/375
0.5
0.5 (0.37)
1.5 (1.1)
3 (2.24)
716/750
1.35
2563/2343
0.5
1 (0.74)
3 (2.2)
5 (3.7)
1290/1350
1.3
8320/7593
0.5
2 (1.5)
5 (3.73)
10 (7.4)
(2)
INPUT SPECIFICATIONS
Description
DR2260Dxxx
DR2260Axxx
Control Voltage Range
4-32 VDC (5)
-32 VDC
90-280 VAC/VDC (6)
Maximum Reverse Voltage
Minimum Turn-On Voltage
Must Turn-Off Voltage
-
90 VAC/VDC
5 VAC/VDC
6 mA
4 VDC
1 VDC
7 mA
Minimum Input Current (for on-state)
Maximum Input Current
15 mA
10 mA
Nominal Input Impedance
Maximum Turn-On Time [msec]
Maximum Turn-Off Time [msec]
Current Limited
1/2 Cycle (7)
1/2 Cycle
Current Limited
20
30
Do not forget to visit us at: www.crydom.com
Copyright © 2019 Crydom Inc. Specifications subject to change without notice.