Monitoring Relays
3-Phase, 3-Phase+N, Multi-function
Types DPB01, PPB01
• 3-phase over and under voltage,
phase sequence and phase loss monitoring relays
• Detect when all 3 phases are present and have the
correct phase sequence
• Detect if all the 3-phase-phase or phase-neutral volt-
ages are within the set limits
• Upper and lower limits separately adjustable
• Measure on own power supply
• Selection of measuring range by DIP-switches
• Adjustable voltage on relative scale
• Adjustable delay function (0.1 to 30 s)
• Output: 8 A SPDT relay N.E.
• For mounting on DIN-rail in accordance with
DIN/EN 50 022 (DPB01) or plug-in module (PPB01)
• 22.5 mm Euronorm housing (DPB01)
or 36 mm plug-in module (PPB01)
DPB01
PPB01
• LED indication for relay, alarm and power supply ON
Product Description
3-phase or 3-phase+neutral points) with built-in time Housing
line voltage monitoring relay delay function.
Ordering Key
DPB 01 C M23
Function
for phase sequence, phase Supply ranges from 208 to Type
loss, over and under voltage 480 VAC covered by two Item number
(separately adjustable set multivoltage relays.
Output
Power supply
Type Selection
Mounting
Output
Supply: 208 to 240 VAC
Supply: 380 to 480 VAC
DIN-rail
Plug-in
SPDT
SPDT
DPB 01 C M23
PPB 01 C M23
DPB 01 C M48
PPB 01 C M48
Input Specifications
Output Specifications
Input
Output
SPDT relay
250 VAC
L1, L2, L3, N
DPB01: Terminals L1, L2, L3, N
PPB01: Terminals 5, 6, 7, 11
Measure on own supply
Rated insulation voltage
Contact ratings (AgSnO2)
Resistive loads
µ
AC 1
DC 12
8 A @ 250 VAC
5 A @ 24 VDC
2.5 A @ 250 VAC
2.5 A @ 24 VDC
≥ 30 x 106 operations
≥ 105 operations
Measuring ranges
208 to 240 VAC
380 to 480 VAC (DPB01CM48) 323 to 550 VAC
380 to 415 VAC (PPB01CM48) 323 to 475 VAC
177 to 275 VAC
Small inductive loads AC 15
DC 13
Mechanical life
Electrical life
Ranges
Upper level
+2 to +22%
of the nominal voltage
-22 to -2%
(at 8 A, 250 V, cos ϕ = 1)
Operating frequency
Dielectric strength
Dielectric voltage
≤ 7200 operations/h
Lower level
of the nominal voltage
2 kVAC (rms)
Rated impulse withstand volt. 4 kV (1.2/50 µs)
Specifications are subject to change without notice (06.11.00)