Monitoring Relays
3-Phase Sequence and Phase Loss
Types DPA01, PPA01
• 3-phase monitoring relays for phase
sequence and phase loss
• Detect when all 3 phases are present and have the
correct sequence
• Measure on own power supply
• Power supply range: 208 to 480 VAC (±15%)
• Output: 8 A SPDT relay or 8 A DPDT normally energized
• For mounting on DIN-rail in accordance with DIN/EN
50 022 (DPA01) or plug-in module (PPA01)
• 22.5 mm Euronorm housing (DPA01) or 36 mm plug-in
module (PPA01)
• LED indication for relay and power supply ON
DPA01D
PPA01
Product Description
Ordering Key
DPA 01 C M44
Housing
3-phase relay for detection of models). For mounting on
incorrect phase sequence, DIN-rail or plug-in module.
total and partial phase loss. The device detects regener-
Supply range from 208 to 480 ated voltages up to 70% of
VAC covered by one multi- the mains nominal voltage
voltage relay (or by two multi- (phase-neutral).
Function
Type
Item number
Output
Power supply
voltage relays for DPA01D
Type Selection
Mounting
Output
Supply: 208-480 VAC
DPA 01 C M44
Supply: 208-240 VAC
DPA 01 D M23
Supply: 380-480 VAC
DPA 01 D M48
DIN-rail
DIN-rail
Plug-in
SPDT
DPDT
SPDT
PPA 01 C M44
Input Specifications
Output Specifications
Input
Output
Rated insulation voltage
Contact ratings (AgSnO2)
DPA01C, PPA01 (SPDT):
SPDT or DPDT relay, N.E.
L1, L2, L3
DPA01: Terminals L1, L2, L3
PPA01: Terminals 5, 6, 7
Measures on own supply
250 VAC
µ
Measuring ranges
Resistive loads
AC 1
DC 12
8 A @ 250 VAC
5 A @ 24 VDC
2.5 A @ 250 VAC
2.5 A @ 24 VDC
208 to 480 VAC (DPA01C) 177 to 550 VAC
208 to 415 VAC (PPA01C) 177 to 475 VAC
208 to 240 VAC (DPA01D) 177 to 275 VAC
380 to 480 VAC (DPA01D) 323 to 550 VAC
Small inductive loads AC 15
DC 13
DPA01D (DPDT):
Resistive loads
Small inductive loads AC 15
DC 13
ON-level
> 70% of the mains phase-
neutral voltage
AC 1
8 A @ 250 VAC
3 A @ 250 VAC
2 A @ 24 VDC
Mechanical life
Electrical life
≥ 30 x 106 operations
≥ 105 operations
(at 8 A, 250 V, cos ϕ = 1)
Operating frequency
≤ 7200 operations/h
Dielectric strength
Dielectric voltage
≥ 2 kVAC (rms)
Rated impulse withstand volt. 4 kV (1.2/50 µs)
Specifications are subject to change without notice (21.10.00)
1