描述
Control/Communicators

D8103 数据手册

 浏览型号D8103的Datasheet PDF文件第2页浏览型号D8103的Datasheet PDF文件第3页浏览型号D8103的Datasheet PDF文件第4页浏览型号D8103的Datasheet PDF文件第5页浏览型号D8103的Datasheet PDF文件第6页浏览型号D8103的Datasheet PDF文件第7页 
D9412G/D7412G  
Specifications  
Control/Communicators  
Control Features  
·
Eight programmable areas, each with  
perimeter/interior partitioning. Regular, master,  
associate, or shared option by area  
·
·
Real-time clock and test timer  
Up to 1000-event log, including time, date and  
event with area, point and user number  
·
Battery charging circuit; AC power, voltage and  
ground fault supervision  
·
·
Automatic reset circuit protectors  
On-board CPU watchdog warning buzzer and  
diagnostic LEDs  
·
·
Lightning and EMI protection  
Power limited external circuits  
User Interface  
·
Supervises up to 8 command centers (up to 32  
non-supervised command centers can be used)  
Communicator  
·
·
·
·
Custom command center text  
D7412G: 4 custom functions  
D9412G: 16 custom functions  
·
·
·
·
Built-in digital communicator with phone line  
monitor (loop or ground start)  
Multiple telephone numbers, primary and duplicate  
paths with main and alternate destinations  
Full function command menu including custom  
functions  
All reports within each 4 route groups are  
programmable  
·
·
·
D7412G: 99 Users  
D9412G: 249 Users  
Optional dual phone line switcher monitors 2 phone  
lines  
Each user has authority by area and 16-character  
name  
·
·
Automatic test and status reports  
Time windows for arming and open/close report  
suppression  
·
14 custom authority levels control user’s authority  
to change, add, delete passcodes or access control  
tokens/cards, disarm, bypass points, initiate system  
tests, and more  
·
Programmable answering machine work-around for  
remote programming on shared phone line  
·
Adjustable brightness/loudness for command  
center display/ sounder  
Programmable Outputs  
·
·
·
·
·
·
·
2-amp alarm power @ 12 VDC  
1.4-amp aux power @ 12 VDC  
4 alarm output patterns  
·
·
D7412G: 1 parallel printer  
D9412G: 3 parallel printers  
Access Control  
Automatic bell test  
·
·
·
·
·
D7412G: 2 access control doors and 396  
tokens/cards  
Programmable bell shut-off timer  
D7412G: 67 programmable outputs  
D9412G: 131 programmable outputs  
D9412G: 8 access control doors and 996  
tokens/cards  
Custom door strike, point shunt and auto disarming  
response by area  
System Response  
·
D7412G: 75 points, 8 on-board, up to 67 off-board  
Logging options for: Access Granted, No Entry,  
Request to Exit and Request to Enter  
·
D9412G: 246 points, 8 on-board, up to 238 off-  
board  
14-panel wide access levels with both manual and  
scheduled control  
·
·
·
·
·
·
31 custom point indexes, including fire supervisory  
Selectable point response time  
Fire alarm verification  
Fire inspector’s local test  
Watch mode  
Scheduled events (Skeds) arm, disarm, bypass and  
unbypass points, control relays, control authority  
levels, control door access and more  

与D8103相关器件

型号 品牌 获取价格 描述 数据表
D8108A ETC

获取价格

Control/Communicators
D8109 ETC

获取价格

Control/Communicators
D8121A ETC

获取价格

Control/Communicators
D8122 ETC

获取价格

Control/Communicators
D8125 ETC

获取价格

Control/Communicators
D8128C ETC

获取价格

Control/Communicators
D8129 ETC

获取价格

Control/Communicators
D8130 ETC

获取价格

Control/Communicators
D8132 ETC

获取价格

Control/Communicators
D8155 AMD

获取价格

2048-Bit Static MOS RAM with I/O Ports and Timer