660 - 1680 Watts
CPB1K/1K5 Series
xppower.com
•
•
•
•
•
•
•
Universal PFC Input
Low Profile (61 mm)
Wide Output Voltage Adjustment
Remote On/Off
Power Good Signal
Remote Sense
Peak Current Available
Specification
Input
General
Input Voltage
Input Frequency
Input Current
Inrush Current
Power Factor
• 85-264 VAC (120-370 VDC)
• 47-63 Hz
Efficiency
Isolation
• See tables
• 3000 VAC Input to Output
2000 VAC Input to Ground
500 VAC Output to Ground
• 19 A at 115 VAC
• 40 A at 230 VAC
Switching Frequency
• 130 ꢀHz PFC, 200 ꢀHz PBꢁ
• 0.98/0.95 at 115/230 VAC
Earth Leakage Current • 1.5 mA max at 230 VAC/60Hz
Environmental
Operating Temperature • -20 ꢃC to ꢄ70 ꢃC, derate linearly from
Output
ꢄ50 ꢃC to 50% at ꢄ70 ꢃC
Output Voltage
Output Voltage Trim
Minimum Load
Start Up Time
Hold Up Time
Drift
• See tables
Relative Humidity
Storage Temperature
Shock
• 20-90% non-condensing
• -20 ꢃC to ꢄ75 ꢃC
• See tables
• No minimum load required
• 400 ms typical at 230 VAC, 100% load
• 20 ms typical at 100% load
• 20 G 11 ms, once each x, y and z axis
Vibration
• 2 G, 10 Hz to 55 ꢀHz, 3 min periods for 60
min along each x, y and z axis
•
•
•
•
0.4% max
Line Regulation
Load Regulation
Ripple & Noise
0.5% max
EMC & Safety
1.0% max 0-100% load
1.0% pꢀ-pꢀ, 20ꢁHz ꢂB
Emissions
• EN55022, level ꢂ conducted
EN55022, level A radiated
Overvoltage Protection • 110-130% Vnom, recycle input to reset
ESD Immunity
Radiated Immunity
EFT/Burst
• EN61000-4-2, level 2 contact, level 3 air
• EN61000-4-3, level 3
Overtemperature
Protection
• Operates in the event of fan failure or if
the operating temperature / derating
criteria is exceeded
• EN61000-4-4, level 3
Surge
• EN61000-4-5, level 3 line to line,
level 4 line to ground
Overload Protection
• Operates at 105% of rated current (101%
of pꢀ rating), <5 s auto recovery,
>5 s recycle input to reset
Safety Approvals
• EN60950, UL60950, cUL (CSA 60950)
Temperature
Coefficient
•
1.25% max -20 ꢃC to ꢄ50 ꢃC
Remote Sense
• Compensates for up to 0.3 V drop max
if not required, sense teminals must be
connected locally i.e ꢄS to ꢄꢁ and
-S to -ꢁ on CN1
Remote On/Off
• 12 V 3 mA applied between RCG &
RC2 will inhibit the output of the unit
and the fan