Power Entry Modules with Line Filter
www.schurter.com/PG06
CG-Bowdencable
With fuseholder 5x20 mm/6.3x32 mm, voltage sel. (series-parallel)
Standard- or Medical-Filter
Fuse drawer, voltage selector insert and Bowden-
cable must be ordered separately.
C14
70° C
Description
- Panel Mount:
Characteristics
- All single elements are already partially wired
- For added safety "Extra-Safe" fuse drawers are available
Fuse drawer meets requirements of medical standard IEC/EN 60601-1
The fuse drawer can only be opened with the aid of a tool
The fuseholder is accessible from the equipment front
- Suitable for use in equipment according to IEC/UL 60950
Suitable for use in medical equipment according to IEC/UL 60601-1
Screw-on mounting from front side
- 5 Functions:
Appliance Inlet, Line switch for bowdencable actuation, Fuseholder
with interchangeable fuse drawer for Fuse-links 5x20 mm or 6.3x32
mm, Voltage Selector (series-parallel), Line filter in standard and medi-
cal version
- Quick connect terminals 4.8 x 0.8 mm
References
Alternative: version without line filter KG-Bowdencable
Alternative: Standard version
Approvals
- VDE Certificate Number: 40004665 (FKSA, FKSB)
- UL File Number: E72928 (FKSA, FKSB)
Weblinks
pdf-datasheet, html-datasheet, General Product Information, Approvals,
CE declaration of conformity, RoHS, CHINA-RoHS, Mating Connectors,
e-Shop, SCHURTER-Stock-Check, Distributor-Stock-Check, CAD-
Drawings, Accessories, Detailed request for product
Technical Data
Ratings IEC
Ratings UL/CSA
Leakage Current
1 - 6A @ Ta 40 °C / 250VAC; 50Hz
1 - 8A @ Ta 40 °C / 125VAC; 60Hz
standard < 0.5mA (250V / 60Hz)
medical < 5 µA (250 V / 60 Hz)
> 1.7kVDC between L-N
> 2.7kVDC between L/N-PE
Test voltage (2sec)
-25°C to 85°C
25/085/21 acc. to IEC 60068-1
from front side IP 40 acc. to IEC 60529
Suitable for appliances with protection
class I acc. to IEC 61140
Quick connect terminals 4.8 x 0.8 mm
Screw: max 8mm
Appliance-Inlet/-Outlet
Fuseholder
C14 acc. to IEC 60320,
UL 498, CSA C22.2 no. 42 (for cold
conditions) pin-temperature 70 °C, 10A,
Protection Class I
1 or 2 pole, Shocksafe category PC2
acc. to IEC 60127-6,
for fuse-links 5 x 20 or 6.3 x 32mm
5 x 20: 2.5W (1 pole)/ 2W (2-pole) per
pole
6.3 x 32: 3.15W (1 pole)/ 2.5W (2-pole)
per pole
Admissible power acceptance at higher
ambient temperature see derating cur-
ves
Switch for bowdencable 2-pole, non-
illuminated, acc. to IEC 61058-1
Technical Details
Dielectric Strength
Rated Power Acceptance @
Ta 23 °C
Allowable Operation Temp.
Climatic Category
Degree of Protection
Protection Class
Power Acceptance @ Ta >
23°C
Terminal
Panel Thickness s
Line Switch
Mounting screw torque max 0.5Nm
Thermoplastic, black, UL 94V-0
Material: Housing
Voltage Selector
Line Filter
series-parallel, 4, 3 or 2 switch positions
or usable as 2-pole change-over switch
Standard and Medical Version, IEC
60939, UL 1283, CSA C22.2 no. 8
Technical Details
MTBF
> 1'100'000h acc. to MIL-HB-217 F
1
Connectors