1/4" x 1-1/4" Fuses
MDA Series, Time Delay, Ceramic Tube
Description
• Time Delay, ceramic tube
RoHS
2002/95/EC
• Optional axial leads available
• 1/4 x 1-1/4 (6.3mm x 32mm) physical size
• Ceramic tube, nickel-plated brass endcap construction
• UL Listed product meets standard 248-14
ELECTRICAL CHARACTERISTICS
Rated Current
Amp Rating
100%
Opening Time
None
1/4 - 30A
135%
200%
60 Minutes Max.
120 Seconds Max.
Dimensions (mm⁄in
Drawing Not to Scale
)
Agency Information
• UL Listed Card: MDA 2/10 - 20A (Guide JDYX,
File E19180)
• UL Recognized Card: MDA 25 - 30A (Guide JDYX2,
File E19180)
• CSA Certification Card: MDA 2/10 - 20
(Class No. 1422-01)
• CSA Component Acceptance: MDA 25-30A
(Class No. 1422-30)
Environmental Data
• Shock: 1/100A and 8/10A – MIL-STD-202,
Method 213, Test Condition I;
1A thru 30A – MIL-STD-202, Method 207,
(HI Shock)
• Vibration: 1/100A and 8/10A – MIL-STD-202,
Method 201; 1/4A thru 30A – MIL-STD-202,
Method 204, Test Condition C (Except 5g, 500HZ)
Ordering
• Specify packaging, product, and option code
SPECIFICATIONS
Product
Code
Voltage
Rating
AC Interrupting
Rating*
250V
35A
35A
35A
DC Interrupting
Typical DC Cold
Resistance**
(ohms)
9.325
Typical
Melting I t†
Typical
Voltage
Drop‡
4.00
1.42
1.31
2
Rating
AC
DC
125V
125V
AC
0.68
2.3
7.8
11.1
25.0
64.0
28.9
40.9
134.0
345.9
534.3
580.3
944.0
1491.3
113.8
206.2
439.5
667.9
997.0
MDA-1/4
MDA-1/2
MDA-3/4
MDA-1
MDA-1-1/2
MDA-2
MDA-2-1/2
MDA-3
MDA-4
MDA-5
MDA-6
MDA-7
MDA-8
MDA-10
MDA-12
MDA-15
MDA-20
MDA-25A
MDA-30A
250V
250V
250V
250V
250V
250V
250V
250V
250V
250V
250V
250V
250V
250V
250V
250V
250V
250V
250V
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
10000A
10000A
10000A
10000A
10000A
10000A
10000A
10000A
10000A
10000A
10000A
10000A
10000A
10000A
10000A
10000A
10000A
10000A
10000A
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1.925
0.8555
0.560
0.2585
0.1645
0.06685
0.0507
35A
1.03
100A
100A
200A
200A
200A
200A
200A
200A
200A
200A
750A
750A
1500A
1500A
1500A
0.691
0.623
0.213
0.182
0.162
0.145
0.141
0.137
0.134
N/A
0.114
0.107
0.095
0.105
0.110
0.0346
0.02355
0.01850
0.01475
0.01230
0.00858
0.00725
0.00543
0.00358
0.00309
0.00243
125V
125V
125V
10000A
10000A
10000A
*
Interrupting Ratings (Measured at 70% - 80% power factor on AC. The interrupting ratings for 25Amp, 30Amp were measured at 90% - 100% power factor on AC)
** DC Cold Resistance (Measured at ≤10% of rated current)
†
‡
Typical Melting I2t (A2Sec) (I2t was measured at listed interrupting rating and rated voltage)
Typical Voltage Drop (Voltage drop was measured at 25°C ambient temperature at rated current)
OC-86