5秒后页面跳转
B3HU-0/A PDF预览

B3HU-0/A

更新时间: 2024-11-10 02:50:35
品牌 Logo 应用领域
爱模 - MSYSTEM /
页数 文件大小 规格书
5页 141K
描述
Space-saving Two-wire Signal Conditioners B3-UNIT

B3HU-0/A 数据手册

 浏览型号B3HU-0/A的Datasheet PDF文件第2页浏览型号B3HU-0/A的Datasheet PDF文件第3页浏览型号B3HU-0/A的Datasheet PDF文件第4页浏览型号B3HU-0/A的Datasheet PDF文件第5页 
MODEL: B3HU  
Space-saving Two-wire Signal  
Conditioners B3-UNIT  
RELATED PRODUCTS  
• USB interface Bell202 modem (model: COP-HU)  
Usable in ‘non-hazardous’ area only.  
• Hand-held communicator  
2-WIRE UNIVERSAL TEMPERATURE TRANSMITTER  
(HART communication, intrinsically safe)  
Functions & Features  
(Consult HART Communication Foundation (HCF) web  
site: www.hartcomm.org. )  
• AMS (version 6.0 or higher)  
• Universal input: mV, V, T/C, RTD, resistance,  
potentiometer and DC voltage  
• Simatic PDM (version 6.0 or higher)  
• PC configurator software (model: B3HUCFG)  
Downloadable at M-System’s web site.  
• High accuracy  
• HART communication  
• Intrinsically safe approval  
GENERAL SPECIFICATIONS  
Construction: Small-sized front terminal structure  
• Programming via hand-held communicator or via PC  
• A wide variety of T/C and RTD types  
• User’s temperature table can be used  
• Self diagnostics  
Connection: Euro type connector terminal  
(Applicable wire size: 0.2 - 2.5 mm  
2
(pin terminals: 0.2 - 1.5  
mm ), stripped length 8 mm)  
2
• Input-output isolated  
Housing material: Flame-resistant resin (gray)  
Isolation: Input to output  
18 (.71)  
Burnout (except DC voltage input): Upscale, downscale or  
no burnout selectable (standard: upscale);  
Also detects wire breakdown and overrange input  
exceeding the electrical design limit for DC voltage input.  
Cold junction compensation (T/C): CJC sensor (included) to  
be attached to the input terminals  
User-configurable items:  
106  
(4.17)  
• Input sensor type  
110.5  
(4.35)  
• Number of wires (RTD & resistance)  
• Input range  
mm (inch)  
• Inverted output  
• Burnout  
• Damping time (via HART only, standard: 0)  
• Sensor calibration (via HART only)  
• Output calibration  
MODEL: B3HU–[1]/A  
ORDERING INFORMATION  
• Code number: B3HU-[1]/A  
• Special linearization data (via HART only)  
• HART communication mode  
Specify a code from below for [1].  
(e.g. B3HU-0/A)  
HART COMMUNICATION  
• Use Ordering Information Sheet (No. ESU-7502). Factory  
standard setting will be used if not otherwise specified.  
• Specify the country in which the product is to be used with  
the Safety Approval code 2.  
Protocol: HART communication protocol  
HART address range: 0 – 15 (factory set to 0)  
Transmission speed: 1200 bps  
Digital current: Approx. 1 mAp-p when communicating  
Character format: 1 Start Bit, 8 Data Bits, 1 Odd Parity Bit,  
1 Stop Bit  
[1] SAFETY APPROVAL  
0: None  
Distance: 1.5 km (0.9 miles)  
1: FM intrinsically safe  
2: ATEX intrinsic safety  
HART communication mode: Master-Slave Mode and Burst  
Mode (factory set to Master-Slave)  
HART network mode: Point-to-Point Mode and Multi-drop  
Mode; automatically set to Multi-drop Mode when the  
address is set to other than 0.  
OPTIONS  
CJC Sensor  
/A: External Sensor (must be specified)  
B3HU SPECIFICATIONS  
ES-7502 Rev.14 Page 1/5  
http://www.m-system.co.jp/  

与B3HU-0/A相关器件

型号 品牌 获取价格 描述 数据表
B3HU-1 MSYSTEM

获取价格

Space-saving Two-wire Signal Conditioners B3-UNIT
B3HU-1/A MSYSTEM

获取价格

Space-saving Two-wire Signal Conditioners B3-UNIT
B3HU-2 MSYSTEM

获取价格

Space-saving Two-wire Signal Conditioners B3-UNIT
B3HU-2/A MSYSTEM

获取价格

Space-saving Two-wire Signal Conditioners B3-UNIT
B3J OMRON

获取价格

Tactile Switch (Hinged Type)
B3J_1 OMRON

获取价格

Tactile Switch (Hinged Type)
B3J_10 OMRON

获取价格

Tactile Switch (Hinged Type)
B3J-1000 OMRON

获取价格

Tactile Switch (Hinged Type)
B3J-1100 OMRON

获取价格

Tactile Switch (Hinged Type)
B3J-1200 OMRON

获取价格

Tactile Switch (Hinged Type)