Thermal-magnetic (TM and AS-line)
AS168XAC4
https://www.schurter.com /PG20
Manual Motor Controller / Circuit Breaker for Equipment thermal-magnetic, 4 poles
See below:
Approvals and Compliances
Description
Applications
- Thermal-magnetic circuit breaker
- High short circuit performance
- Availability of AC and DC in the same frame size
- DIN-Rail Mounting
- Industrial appliances
References
Last order possibility: 31.08.2018
Last delivery date: 30.09.2018
Weblinks
pdf datasheet, html-datasheet, General Product Information, Distributor-
Stock-Check, Detailed request for product, Product News
Technical Data
General data
Tripping Type
Positively trip free
Rated Voltage AC
IEC : 420 V Y / 240 V; 50/60 Hz
Actuation Type
Manual ON/OFF
UL/CSA : 480 V Y / 277 V; 50/60 Hz
65 V
Permissible wire cross section 1.5 - 25 mm² / 16 - 4 AWG
Rated Voltage DC
Rated current
Switched neutral
0.5 - 52 A , see approbations
Rated Voltage
Rated current
Function
AC 277 V
AC/DC 65 A
The switched neutral closes with ma-
nual closure of the poles and opens
automatically with thermal magnetic
tripping of the poles.
Conditional short circuit capa- Icn: AC 420 V Y/240 V / DC 65 V: 5 kA
city IEC 60934 (no fuse)
Conditional short circuit capa- Inc: AC 480 V Y/277 V: 10 kA (with fuse
city UL 1077
class H/J, 4x rated current (min. 15 A))
Icn: AC 480 V Y/277 V: 5 kA (no fuse)
Icn: DC 65 V: 2 kA (no fuse)
Conditional short circuit capa- Icn: AC 480 V Y/277 V: 5 kA (no fuse)
city UL 508
Add-on modules
Add-on modules
Technical data for the additional module
see separate data sheet
Degree of Protection
Lifetime
Dielectric Strength
from front side IP 40 acc. to IEC 60529
1 x Ir 6000switching cycles
50Hz: > 2kV
Impulse 1.2/50 μs
Vibration Resistance
0.75 mm ꢀ 5 - 60 Hz
acc. to IEC 60068-2-6, test Fc
10 G ꢀ 60 - 500 Hz
acc. to IEC 60068-2-6, test Fc
250/440VAC > 5 MΩ
30 G / 18ms
Insulation Resistance
Shock Resistance
acc. to IEC 60068-2-27, test Ea
Ambient temperature
Weight
-10°C to 55°C
100 - 130g
Approvals and Compliances
Detailed information on product approvals, code requirements, usage instructions and detailed test conditions can be looked up in Details about
Approvals
1