POSEICO SPA
Via Pillea 42-44, 16153 Genova - ITALY
Tel. + 39 010 8599400 - Fax + 39 010 8682006
Sales Office:
Tel. + 39 010 8599400 - sales@poseico.com
PHASE CONTROL MODULE
ADT200HVI
Repetitive voltage up to
Mean forward current
Surge current
5800 V
200 A
4,5 kA
FINAL SPECIFICATION
apr 17 - ISSUE : 02
Tj
[°C]
Symbol
Characteristic
Conditions
Value
Unit
BLOCKING
V RRM
Repetitive peak reverse/off-state voltage
Non-repetitive peak reverse voltage
Repetitive peak reverse/off-state current
125
125
125
5800
5900
70
V
V
V RSM
I
I
RRM/DRM
mA
CONDUCTING
T (AV)
Mean forward current
180° sin, 50 Hz, Th=85°C, double side cooled
180° sin, 50 Hz, Tc=55°C, double side cooled
200
A
I
I
T (AV)
TSM
Mean forward current
Surge forward current
I² t
288
4,5
A
kA
Sine wave, 10 ms
without reverse voltage
125
x 103
I² t
101
1,88
A²s
V
V T
On-state voltage
Threshold voltage
On-state slope resistance
On-state current =
150 A
25
V T(TO)
125
125
1,45
V
r
T
2,850
mohm
SWITCHING
From 75% VDRM up to 1050 A; gate 10V, 5W
di/dt
Critical rate of rise of on-state current, min.
125
200
A/µs
dv/dt
Critical rate of rise of off-state voltage, min.
Gate controlled delay time, typical
Circuit commutated turn-off time, typical
Reverse recovery charge
Linear ramp up to 70% of VDRM
125
25
500
1,6
V/µs
µs
VD=100V; gate source 25V, 10W , tr=.5 µs
t
t
d
q
dv/dt = 20 V/µs linear up to 75% VDRM
di/dt = -20 A/µs, I= 700 A
VR= 50 V
500
µs
Q rr
125
µC
A
I
I
I
rr
Peak reverse recovery current
Holding current, typical
H
VD=5V, gate open circuit
VD=5V, tp=30µs
25
25
300
700
mA
mA
L
Latching current, typical
GATE
V GT
Gate trigger voltage
VD=5V
25
2,50
V
I
GT
Gate trigger current
VD=5V
25
250
0,25
30
mA
V
V GD
Non-trigger gate voltage, min.
Peak gate voltage (forward)
Peak gate current
VD=VDRM
125
V FGM
V
I
FGM
10
A
V RGM
P GM
P G
Peak gate voltage (reverse)
Peak gate power dissipation
Average gate power dissipation
5
V
Pulse width 100 µs
150
2
W
W
MOUNTING
R th(j-h)
Thermal impedance, DC
Junction to case, per element
Case to heatsink, per element
70,0
°C/kW
R th(c-h)
T j
Thermal impedance
Operating junction temperature
RMS insulation voltage
Mounting torque
20,0
-30 / 125
6000
°C/kW
°C
V ins
T
50 hz , circuit to base, all terminal shorted
Case to heatsink
25
V
4 to 6
kN
kN
g
T
Mounting torque
Busbars to terminal
12 to 18
1500
Mass
ORDERING INFORMATION : ADT200HVI S 58
VRRM/100
standard specification