描述
Limit Alarms (potentiometer adj.) A-UNIT

ACV-15112-R 数据手册

 浏览型号ACV-15112-R的Datasheet PDF文件第1页浏览型号ACV-15112-R的Datasheet PDF文件第3页浏览型号ACV-15112-R的Datasheet PDF文件第4页 
MODEL: ACV  
For maximum relay life with inductive loads, external  
[5] OPTIONS  
blank: none  
protection is recommended.  
/Q: With options (specify the specification)  
Alarm Trip Operation Terminal No. in parentheses  
(9-11)ON  
Output 1  
(9-10)ON  
SPECIFICATIONS OF OPTION: Q (multiple selections)  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
(1-3)ON  
Output 2  
(1-2)ON  
/C02: Polyurethane coating  
Input  
(%)  
/C03: Rubber coating  
0
50  
100  
TERMINAL SCREW MATERIAL  
/S01: Stainless steel  
Output 2  
Setpoint  
Output 1  
Setpoint  
Trip Operation in Power Failure  
Output Code: 1 & 4: Terminals 1 – 2, 9 – 10 turn ON  
Output Code: 2 & 3: Terminals 1 – 3, 9 – 11 turn ON  
GENERAL SPECIFICATIONS  
Construction: Plug-in  
Connection: M3.5 screw terminals  
Screw terminal: Chromated steel (standard) or stainless  
steel  
INSTALLATION  
Power input  
Housing material: Flame-resistant resin (black)  
Isolation: Input to output 1 to output 2 to power  
Zero adjustment: -5 to +5 % (front)  
AC: Operational voltage range: rating ±10 %,  
50/60 ±2 Hz, approx. 2 VA  
DC: Operational voltage range: rating ±10 %, or 85 – 150  
V for 110 V rating (ripple 10 % p-p max.)  
approx. 2 W (80 mA at 24 V)  
Span adjustment: 95 to 105 % (front)  
Setpoint adjustments: 270°-turn screwdriver adjustments  
(front); 0 – 100 % independently  
Operating temperature: -5 to +60°C (23 to 140°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Mounting: Surface or DIN rail  
Hysteresis (deadband) adjustments: 1 – 100 % (front)  
Front LEDs: LED turns on at a tripped condition; red for  
output 1, green for output 2  
Weight: 450 g (0.99 lb)  
Power ON timer: Relays de-energized for approx. 2 seconds  
after power is turned on.  
PERFORMANCE in percentage of span  
Trip point repeatability: ±0.5 %  
INPUT SPECIFICATIONS  
DC Current:  
Temp. coefficient: ±0.05 %/°C (±0.03 %/°F)  
Response time: ≤ 0.5 sec. (0 – 100 % at 90 % setpoint)  
Line voltage effect: ±0.1 % over voltage range  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 2000 V AC @1 minute (input to output 1  
to output 2 to power to ground)  
Shunt resistor attached to the input terminals (0.5 W)  
Specify input resistance value for code Z.  
DC Voltage: -300 – +300 V DC  
Minimum span: 10 mV  
Offset: Max. 1.5 times span  
Input resistance  
Span 10 – 100 mV : ≥ 10 kΩ  
Span 0.1 – 1 V : ≥ 100 kΩ  
Span ≥ 1 V : ≥ 1 MΩ  
OUTPUT SPECIFICATIONS  
Relay Contact: 100 V AC @ 1 A (cos ø = 1)  
120 V AC @ 1 A (cos ø = 1)  
240 V AC @ 0.5 A (cos ø = 1)  
30 V DC @ 1 A (resistive load)  
Maximum switching voltage: 380 V AC or 125 V DC  
Maximum switching power: 120 VA or 30 W  
Minimum load: 5 V DC @ 10 mA  
Mechanical life: 5 x 10 cycles  
7
ACV SPECIFICATIONS  
ES-2117 Rev.7 Page 2/4  
http://www.m-system.co.jp/  

与ACV-15112-R相关器件

型号 品牌 获取价格 描述 数据表
ACV-15112-R/Q MSYSTEM

获取价格

Limit Alarms (potentiometer adj.) A-UNIT
ACV-15112-S MSYSTEM

获取价格

Limit Alarms (potentiometer adj.) A-UNIT
ACV-15112-S/Q MSYSTEM

获取价格

Limit Alarms (potentiometer adj.) A-UNIT
ACV-15112-V MSYSTEM

获取价格

Limit Alarms (potentiometer adj.) A-UNIT
ACV-15112-V/Q MSYSTEM

获取价格

Limit Alarms (potentiometer adj.) A-UNIT
ACV-15113-B MSYSTEM

获取价格

Limit Alarms (potentiometer adj.) A-UNIT
ACV-15113-B/Q MSYSTEM

获取价格

Limit Alarms (potentiometer adj.) A-UNIT
ACV-15113-C MSYSTEM

获取价格

Limit Alarms (potentiometer adj.) A-UNIT
ACV-15113-C/Q MSYSTEM

获取价格

Limit Alarms (potentiometer adj.) A-UNIT
ACV-15113-D MSYSTEM

获取价格

Limit Alarms (potentiometer adj.) A-UNIT