Panel Mount
Datasheet
GN Series
AC Output SSRs
• Current rating 10 and 125 Amps
• Output voltage 24-280 VAC and 48-660 VAC
• Available with or without IP20 touch-safe cover
• LED Input Status Indicator
• UL Approved, CE Compliant to EN60950-1
• Improved SEMS screw and washer
• Redesigned housing with anti-rotation barriers
• EMC Compliant to level 3
For Generation 3 datasheet click here
PRODUCT SELECTION
Control Voltage
3-32 VDC
18-36 VAC
90-280 VAC
10 A
84134000
84134002
84134001
25 A
84134010
84134012
84134011
50 A
84134020
84134022
84134021
75 A
84134030
84134032
84134031
100 A
84134040
84134042
84134041
125 A
84134080
84134082
84134081
Operating Voltage
AVAILABLE OPTIONS
0: 24-280 VAC/Zero Voltage Turn-On
1: 48-660 VAC/Zero Voltage Turn-On
2: 24-280 VAC/Instantaneous Turn-On
3: 48-660 VAC/Instantaneous Turn-On
Thermal Pad
Blank: Not included
H: Included
Series
8413
4
0
1
U0
H
Control Voltage
0: 3-32 VDC
Rated Load
Touch Safe Cover
4: Not included (IP00)
7: Included (IP20)
Current
1: 90-280 VAC
2: 18-36 VAC
Required for valid part number
0: 10 Amps
1: 25 Amps
2: 50 Amps
3: 75 Amps
4: 100 Amps
8: 125 Amps
For options only and not required for valid part number
Not all part number combinations are available.
Contact Crydom Technical Support for information on
the availability of a specific part number.
>
OUTPUT SPECIFICATIONS (1)
Description
Operating Voltage (47-440Hz) [Vrms]
Transient Voltage [Vpk] (2)
280 VAC
660 VAC
24-280
600
48-660
1200
0.25
Maximum Off-State Leakage Current @ Rated Voltage [mArms]
Minimum Off-State dv/dt @ Maximum Rated Voltage [V/µsec]
0.1
500
500
OUTPUT SPECIFICATIONS (1)
Description
10 A
25 A
50 A
75 A
100 A
125 A
Maximum Load Current [Arms] (3)
10
25
50
75
100
125
Minimum Load Current [mArms]
500
50
100
100
100
100
Maximum 1 Cycle Surge Current (50/60Hz) [Apk]
1 Second surge current (Apk. Ta=25°C) 50/60 Hz
Maximum On-State Voltage Drop @ Rated Current [Vpk]
Thermal Resistance Junction to Case (Rjc) [°C/W]
Maximum 1/2 Cycle I² t for Fusing (50/60Hz) [A² sec]
Minimum Heat Sink for Rated Current @ 40°C [°C/W]
150/175
50
1.35
0.4
110/120
5
275/300
85
1.35
0.4
380/370
2
710/750
150
1.35
0.25
2520/2320
1
1050/1100
225
1.3
0.16
5500/5000
0.7
1120/1200
300
1.3
0.16
6270/6000
0.5
1600/1700
375
1.25
0.11
12800/12050
0.5
Do not forget to visit us at: www.crydom.com
Copyright © 2016 Crydom Inc. Specifications subject to change without notice.